Field Setting
Si39-504
136
Test Operation
3.2.2
Cool / Heat Mode Switching
There are the following 4 cool/heat switching modes.
c
Set cool/heat separately for each outdoor unit system by indoor unit remote controller.
d
Set cool/heat separately for each outdoor unit system by cool/heat switching remote
controller.
e
Set cool/heat for more than one outdoor unit system simultaneously in accordance with
unified master outdoor unit by indoor unit remote controller.
f
Set cool/heat for more than one outdoor unit system simultaneously in accordance with
unified master outdoor unit by cool/heat switching remote controller.
c
Set Cool / Heat Separately for Each Outdoor Unit System by Indoor Unit Remote Controller
It does not matter whether or not there is outdoor - outdoor unit wiring.
Set outdoor unit PC board DS1-1 to IN (factory set).
Set cool/heat switching to IND (individual) for “Setting mode 1” (factory set).
Set the master unit (= indoor unit having the right to select the cooling/heating operation
mode).
<Set the master unit (= indoor unit having the right to
select the cooling/heating operation mode).>
In the case of wired remote controllers
• After the check operation,
“CHANGEOVER UNDER
CONTROL”
is flashing in all connected remote controllers.
• Select an indoor unit to be used as the master unit in
accordance with the request from the customer.
(It is recommended to select an indoor unit which will be
used most often as the master unit.)
• Press the operation mode selector button in the remote
controller of the indoor unit selected as the master unit.
• In that remote controller,
“CHANGEOVER UNDER
CONTROL”
disappears. That remote controller will control
changeover of the cooling/heating operation mode.
• In other remote controllers,
“CHANGEOVER UNDER
CONTROL”
lights.
For the details, refer to the installation manual
supplied together with the indoor unit.
In the case of wireless remote controllers
• After the check operation, the timer lamp is flashing in all
connected indoor units.
• Select an indoor unit to be used as the master unit in
accordance with the request from the customer.
(It is recommended to select an indoor unit which will be
used most often as the master unit.)
• Press the operation selector mode button in the remote
controller of the indoor unit selected as the master unit. A
“peep” sound is emitted, and the timer lamp turns off in all
indoor units.
• That indoor unit will control changeover of the cooling/
heating operation mode.
Содержание VRV II RXYQ5MATL
Страница 20: ...Si39 504 Specifications 9 Part 2 Specifications 1 Specifications 10 1 1 Outdoor Units 10 1 2 Indoor Units 21...
Страница 53: ...Specifications Si39 504 42 Specifications...
Страница 56: ...Si39 504 Refrigerant Circuit Refirgerant Circuit 45 RXYQ5MA 3D048203 2 4 3 5 K J S E D M T N P A G O 1 W V...
Страница 115: ...Outline of Control Indoor Unit Si39 504 104 Function...
Страница 161: ...Field Setting Si39 504 150 Test Operation...
Страница 172: ...Si39 504 Troubleshooting by Remote Controller Troubleshooting 161...
Страница 265: ...Piping Diagrams Si39 504 254 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ5MAYL E TL E 3D048203...
Страница 266: ...Si39 504 Piping Diagrams Appendix 255 RXYQ8MA 10MA 12MAYL E TL E 3D048033A...
Страница 267: ...Piping Diagrams Si39 504 256 Appendix RXYQ14MA 16MAYL E TL E 3D048034A...
Страница 271: ...Wiring Diagrams for Reference Si39 504 260 Appendix RXYQ8MA 10MA 12MAYL E 3D047088C...
Страница 272: ...Si39 504 Wiring Diagrams for Reference Appendix 261 RXYQ14MA 16MAYL E 3D047089C...
Страница 273: ...Wiring Diagrams for Reference Si39 504 262 Appendix 2 1 2 RXYQ MATL E RXYQ5MATL E 3D049059A...
Страница 274: ...Si39 504 Wiring Diagrams for Reference Appendix 263 RXYQ8MA 10MA 12MATL E 3D049060A...
Страница 275: ...Wiring Diagrams for Reference Si39 504 264 Appendix RXYQ14MA 16MATL E 3D049061A...
Страница 277: ...Wiring Diagrams for Reference Si39 504 266 Appendix RXYQ18MA 20MA 22MA 24MA 26MA 28MA 30MA 32MAYL E 3D040747H...
Страница 278: ...Si39 504 Wiring Diagrams for Reference Appendix 267 RXYQ34MA 36MA 38MA 40MA 42MA 44MA 46MA 48MAYL E C 3D040748H...
Страница 279: ...Wiring Diagrams for Reference Si39 504 268 Appendix 2 2 2 RXYQ MATL E RXYQ5MA 8MA 10MA 12MA 14MA 16MATL E 3D041990A...
Страница 280: ...Si39 504 Wiring Diagrams for Reference Appendix 269 RXYQ18MA 20MA 22MA 24MA 26MA 28MA 30MA 32MATL E 3D041991A...
Страница 281: ...Wiring Diagrams for Reference Si39 504 270 Appendix RXYQ34MA 36MA 38MA 40MA 42MA 44MA 46MA 48MATL E 3D041992A...
Страница 282: ...Si39 504 Wiring Diagrams for Reference Appendix 271 2 3 Indoor Unit FXCQ20M 25M 32M 63MVE 3D039556A...
Страница 283: ...Wiring Diagrams for Reference Si39 504 272 Appendix FXCQ40M 50M 80M 125MVE 3D039557A...
Страница 284: ...Si39 504 Wiring Diagrams for Reference Appendix 273 FXFQ25M 32M 40M 50M 63M 80M 100M 125MVE 3D039600A...
Страница 285: ...Wiring Diagrams for Reference Si39 504 274 Appendix FXKQ25M 32M 40M 63MVE 3D039564B...
Страница 286: ...Si39 504 Wiring Diagrams for Reference Appendix 275 FXDQ20N 25N 32N 40N 50N 63NVE with Drain Pump 3D045500C...
Страница 287: ...Wiring Diagrams for Reference Si39 504 276 Appendix FXDQ20N 25N 32N 40N 50N 63NVET without Drain Pump 3D049604A...
Страница 288: ...Si39 504 Wiring Diagrams for Reference Appendix 277 FXSQ20M 25M 32M 40M 50M 63M 80M 100M 125MVE 3D039561A...
Страница 289: ...Wiring Diagrams for Reference Si39 504 278 Appendix FXMQ40M 50M 63M 80M 100M 125MVE 3D039620B...
Страница 290: ...Si39 504 Wiring Diagrams for Reference Appendix 279 FXMQ200M 250MVE 3D039621B...
Страница 291: ...Wiring Diagrams for Reference Si39 504 280 Appendix FXHQ32M 63M 100MVE 3D039801D...
Страница 292: ...Si39 504 Wiring Diagrams for Reference Appendix 281 FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206C...
Страница 309: ...Selection of Pipe Size Joints and Header Si39 504 298 Appendix Note 1...
Страница 315: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 504 304 Appendix...