Check
SiUS342303E
385
Part 6 Service Diagnosis
4.10 Broken Wire Check of the Relay Wires
CHECK 15
1. Procedure for checking outdoor-outdoor unit transmission wiring for broken wires
On the system shown below, turn OFF the power supply to all equipment, short circuit between
the outdoor-outdoor unit terminal F1 and F2 in the "Outdoor Unit A" that is farthest from the
central remote controller, and then conduct continuity checks between the transmission wiring
terminal blocks F1 and F2 of the central remote controller using a multimeter. If there is
continuity between the said terminal blocks, the outdoor-outdoor unit transmission wiring has no
broken wires in it.
If there is no continuity, the transmission wiring may have broken wires. With the
outdoor-outdoor unit terminal of the "Outdoor Unit A" short circuited, conduct continuity checks
between the transmission wiring terminal blocks F1 and F2 of the unified ON/OFF controller. If
there is no continuity as well, conduct continuity checks between the outdoor-outdoor unit
terminal of the "Outdoor Unit E", between the outdoor-outdoor unit terminal of the "Outdoor Unit
D", between the outdoor-outdoor unit terminal of the "Outdoor Unit C", … in the order described,
thus identifying the place with continuity.
If the place with continuity can be identified, there may be broken wires in places before the said
place with continuity.
2. Procedure for checking indoor-outdoor unit transmission wiring for broken wires (for checking
the indoor-outdoor unit transmission wiring of the "Outdoor Unit C" for broken wires)
Turn OFF the power supply to all equipment, short circuit between the indoor-outdoor unit
terminal F1 and F2 in the "Outdoor Unit C, and then conduct continuity checks between the
transmission wirings F1 and F2 of the "Indoor Unit a" that is farthest from the "Outdoor Unit C"
using a multimeter. If there is continuity between the said transmission wirings, the
indoor-outdoor unit transmission wiring has no broken wires in it.
If there is no continuity, the transmission wiring may have broken wires. With the indoor-outdoor
unit terminal of the "Outdoor Unit C" short circuited, identify the place with continuity in the
transmission wiring of the "Indoor Unit b", transmission wiring of the "Indoor Unit c", and
transmission wiring of the "Indoor Unit d" in the order described.
If the place with continuity can be identified, there may be broken wires in places before the said
place with continuity.
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...