Troubleshooting by Error Code
SiUS342303E
311
Part 6 Service Diagnosis
Reference
3.40 Electronic Expansion Valve Coil Abnormality or Sub PCB
Momentary Overcurrent
Applicable
Models
All outdoor unit models
Error Code
E9
Method of Error
Detection
Detects according to whether or not there is continuity across the electronic expansion valve coils.
Error Decision
Conditions
When no current flows through common (COM[+]) at the time of turning ON the power supply.
Supposed
Causes
Disconnection of connectors from electronic expansion valves
Defective electronic expansion valve coil
Defective outdoor unit main PCB
Sub PCB momentary overcurrent
Troubleshooting
CHECK 18
Refer to page 390.
Turn OFF the power supply
once, and then turn it ON again.
Return to normal?
Investigate external causes other than
failures (e.g. noise).
YES
NO
Connector for
the electronic expansion
valve of the outdoor unit
is connected.
Properly and securely connect the
connector.
NO
YES
Replace the electronic expansion
valve.
NO
Replace the outdoor unit main PCB
(A1P).
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check for electronic expansion valves applicable to the error code
E9
while in monitor mode.
Sub code:
E9-01/05: Y1E (Master/Sub)
E9-03/06: Y2E (Master/Sub)
E9-04/07: Y3E (Master/Sub)
E9-26/27: Y4E (Master/Sub)
E9-29/34: Y5E (Master/Sub)
E9-11/12: Y6E (Master/Sub)
E9-57/58: Y6E (Master/Sub)
The
resistance of the
electronic expansion
valve coil is normal.
CHECK 18
YES
Replace the outdoor unit sub PCB
(A8P).
YES
Is the error code
E9-57/58?
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...