Troubleshooting by Error Code
SiUS342303E
309
Part 6 Service Diagnosis
3.39 Outdoor Fan Motor Abnormality
Applicable
Models
All outdoor unit models
Error Code
E7
Method of Error
Detection
Detects according to the value of current flowing through the fan PCB.
Error Decision
Conditions
Overcurrent is detected from the fan PCB (Detecting overcurrent 4 times will shut down the
system).
Current does not increase at fan motor startup or while the fan motor is in operation (Detecting 4
times will shut down the system).
Supposed
Causes
Fan motor failure
Neglect to connect or defective connection of harness/connector between the fan motor and the
PCB
Fan does not rotate due to foreign matter caught in it.
Clearing condition: fan motor performs normal operation for a period of 5 minutes
Troubleshooting
There are
foreign matter around the
applicable fan.
Remove the foreign matter.
YES
Check for the connections of all fan motor connectors.
NO
Turn OFF the power supply, and then wait for a period of 10 minutes.
Some connectors are
disconnected.
Insert the connector.
YES
NO
NO
There is a relay
connection error.
Correct the connection of the
relay harness.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
A
Check for any wire connection errors in 2 fan motors.
M1F: Connectors are white both on the PCB side and motor side.
M2F: Connectors are white on the PCB side and red on the motor side.
Check for Connection of Connector
Check for Colors of Connectors
There is no
continuity across the fuse
(F101U) on the fan
PCB.
Replace the fan PCB.
YES
NO
For models equipped with 2 fan motors, check the fan motor
M1F or M2F applicable to the error code
E7
while in monitor
mode of the outdoor unit.
Check in Monitor Mode
Go to the next page.
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...