SiUS342303E
Troubleshooting by Error Code
Part 6 Service Diagnosis
298
Note(s)
3.31 Remote Controller Thermistor Abnormality
Applicable
Models
All indoor unit models
Error Code
CJ
Method of Error
Detection
Error detection is carried out by the temperature detected by the remote controller thermistor.
Error Decision
Conditions
The remote controller thermistor becomes disconnected or shorted while the unit is running.
Error code is displayed but the system operates continuously.
Supposed
Causes
Defective remote controller thermistor
Defective remote controller PCB
Troubleshooting
1: How to delete the history of error codes.
Press the
ON/OFF
button for 4 seconds and more while the error code is displayed in the
inspection mode.
Clear the error code history.
(
∗
1) (
W
hile in inspection mode,
press and hold the
ON/OFF
button for a period of 4
seconds or more.)
YES
YES
Is
CJ
displayed on the remote
controller?
Is the field
setting 10 (20)-2
correct?
YES
YES
Is a remote
controller
w
ith group control
being used?
Is the field
setting 10 (20)-6 set
to
02
?
Caution
Be sure to turn off the po
w
er s
w
itch before connecting or disconnecting
connectors, or parts may be damaged.
Correct the field setting.
External factor other than
equipment error.
(for example, noise etc.)
N
O
N
O
Replace the remote
controller.
Set 10 (20)-6 to
02
.
Replace the remote
controller.
N
O
N
O
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...