SiUS342303E
Symptom-based Troubleshooting
Part 6 Service Diagnosis
226
1. Symptom-based Troubleshooting
1.1 General
Troubleshooting
Symptom
Supposed Cause
Countermeasure
1
The system does not start operation at all.
Blowout of fuse(s)
Turn OFF the power supply and then
replace the fuse (s).
Cutout of breaker(s)
• If the knob of any breaker is in its
OFF position, turn ON the power
supply.
• If the knob of any circuit breaker is
in its tripped position, do not turn ON
the power supply.
Power failure
After the power failure is reset, restart
the system.
The connector loose or not fully
plugged in
Turn off the power supply to verify the
connection of the connector.
2
The system starts operation but makes an
immediate stop.
Blocked air inlet or outlet of indoor or
outdoor unit
Remove obstacle(s).
Clogged air filter(s)
Clean the air filter(s).
3
The system does not cool or heat air well.
Blocked air inlet or outlet of indoor or
outdoor unit
Remove obstacle(s).
Clogged air filter(s)
Clean the air filter(s).
Enclosed outdoor unit(s)
Remove the enclosure.
Improper set temperature
Set the temperature to a proper
degree.
Airflow rate set to LOW
Set it to a proper airflow rate.
Improper direction of air diffusion
Set it to a proper direction.
Open window(s) or door(s)
Shut it tightly.
IN COOLING
Direct sunlight received
Hang curtains or shades on windows.
IN COOLING
Too many persons staying in a room
The model must be selected to match
the air conditioning load.
IN COOLING
Too many heat sources (e.g. OA
equipment) located in a room
IN DRYING
The reason is that the dry operation
serves not to reduce the room
temperature where possible.
Change the system to cooling
operation.
4
The system does
not operate.
The system stops and
immediately restarts operation.
If the operation lamp on the remote
controller turns ON, the system will
be normal. These symptoms indicate
that the system is controlled so as not
to put unreasonable loads on the
system.
Normal operation. The system will
automatically start operation after a
lapse of five minutes.
Pressing the temperature
setting button immediately
resets the system.
The remote controller displays
CENTRAL CONTROL,
which
blinks for a period of several
seconds when the
OPERATION
button is
depressed.
The system is controlled with
centralized controller. Blinking
display indicates that the system
cannot be operated using the remote
controller.
Operate the system using the
COOL/HEAT central remote
controller.
The system stops immediately
after turning ON the power
supply.
The system is in preparation mode of
microcomputer operation.
Wait for a period of approximately
one minute.
5
The system
makes
intermittent stops.
The remote controller displays
error codes
U4
or
U5,
and the
system stops but restarts after
a lapse of several minutes.
The system stops due to an
interruption in communication
between units caused by electrical
noises coming from equipment other
than air conditioners.
Remove causes of electrical noises.
If these causes are removed, the
system will automatically restart
operation.
O
N
Knob
Tripped
OFF
Circuit breaker
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...