SiUS342303E
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
180
1.7 List of Field Settings for Outdoor-Air Processing Unit
: Factory setting
1.8 Setting of Operation Control Mode
The operation control mode is compatible with a variety of controls and operations by limiting the
functions of the operation remote controller. Furthermore, operations such as remote controller
ON/OFF can be limited in accordance with the combination conditions. (Refer to information on the
next page.)
Central remote controller is normally available for operations. (Except when centralized monitor is
connected)
20 modes consisting of combinations of the following 5 operation modes with temperature and
operation mode setting by remote controller can be set and displayed by operation modes 0
through 19.
ON/OFF control impossible by remote controller
Used when you want to turn ON/OFF by central remote controller only. (Cannot be turned
ON/OFF by remote controller.)
OFF control only possible by remote controller
Used when you want to turn ON by central remote controller only, and OFF by remote controller
only.
Centralized
Used when you want to turn ON by central remote controller only, and turn ON/OFF freely by
remote controller during set time.
Individual
Used when you want to turn ON/OFF by both central remote controller and remote controller.
Timer operation possible by remote controller
Used when you want to turn ON/OFF by remote controller during set time and you do not want
to start operation by central remote controller when time of system start is programmed.
Dip switch
DS3
Heating
Speed Tap
A
—
—
OFF
OFF
B
—
—
ON
OFF
C
—
—
OFF
ON
D
—
—
ON
ON
Mode
No.
First
Code
No.
Setting Contents
Second Code No.
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
10
(20)
0
Filter contamination
2500 hr
1250 hr
—
—
—
—
—
—
—
—
—
—
—
—
—
3
Display time to clean
air filter calculation
Display
No
display
—
—
—
—
—
—
—
—
—
—
—
—
—
12
(22)
1
External ON/OFF
input
Forced
OFF
ON/OFF
control
—
—
—
—
—
—
—
—
—
—
—
—
—
5
Power failure
automatic reset
Not
equipped
Equipped
—
—
—
—
—
—
—
—
—
—
—
—
—
14
(24)
3
Discharge pipe
temperature
(cooling)
°C
13
14
15
16
17
18
19
20
21
22
23
24
25
°F
55.4
57.2
59 60.8 62.6
64.4
66.2 68 69.8 71.6 73.4 75.2
77
4
Discharge pipe
temperature
(heating)
°C
18
19
20
21
22
23
24
25
26
27
28
29
30
°F
64.4
66.2
68 69.8 71.6 73.4 75.2
77
78.8 80.6 82.4 84.2
86
Contents of Control Modes
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...