Field Settings for Indoor Unit
SiUS342303E
149
Part 5 Field Settings and Test Operation
1. Field Settings for Indoor Unit
1.1 Field Settings with Remote Controller
Individual function of indoor unit can be changed from the remote controller. At the time of
installation or after service inspection / repair, make the field setting in accordance with the
following description. Wrong setting may cause error. (When optional accessory is mounted on the
indoor unit, setting for the indoor unit may be required to change. Refer to information in the option
handbook.)
1.1.1 BRC1E73
<Basic screen>
(1)
<Service Settings menu screen>
(2)
Press
Menu/OK
button.
<Service Settings screen>
(3)
(4)
(5)
(3)
(5)
Press
Menu/OK
button.
FIRST CODE (SW) NO.
SECOND CODE NO.
Press and hold
Cancel
button for 4 seconds or
more during backlight lit.
In the case of individual
setting per indoor unit
In the case of group total
setting
1.
Press and hold
Cancel
bu
tton for
4 seconds or more.
Ser
v
ice settings men
u
is
displayed.
2.
Select
Field Settings
in the
Ser
v
ice Settings men
u
, and
press
Menu/OK
bu
tton.
Field settings screen is
displayed.
3.
Highlight the mode, and select
desired
Mode No.
b
y
u
sing
(Up/Down)
bu
tton.
4.
In the case of setting per indoor
u
nit d
u
ring gro
u
p control (When
Mode No. s
u
ch as
20
,
21
,
22
,
23
,
25
are selected), highlight the
u
nit No. and select
Indoor unit
No.
to
b
e set
b
y
u
sing
(Up/Down)
bu
tton.
(In the case of gro
u
p total setting,
this operation is not needed.)
5.
Highlight SECOND CODE NO. of
the FIRST CODE NO. to
b
e
changed, and select desired
SECOND CODE NO.
b
y
u
sing
(Up/Down)
bu
tton. M
u
ltiple
identical mode n
u
m
b
er settings
are a
v
aila
b
le.
In the case of indi
v
id
u
al setting
per indoor
u
nit, c
u
rrent settings
are displayed. And, SECOND
CODE NO. “ - ” means no
f
u
nction.
In case of setting for all indoor
u
nits in the remote control
gro
u
p, a
v
aila
b
le SECOND
CODE NO. is displayed as “
∗
”
which means it can
b
e
changed.
When SECOND CODE NO. is
displayed as “ - ”, there is no
f
u
nction.
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...