SiUS372201EB
Basic Control
Part 4 Functions and Control
150
5.2 Compressor PI Control
Carries out the compressor capacity PI control so that Te reaches the target value during cooling
and Tc during heating.
Cooling
Controls compressor capacity to adjust Te to achieve target value (TeS).
1. VRT control (default)
When the indoor temperature approaches the set temperature in all indoor units and the
required capacity decreases, TeS is automatically increased to adjust the capacity.
2. Constant control
TeS is fixed to the set value.
Te setting
Te: Low pressure equivalent saturation temperature
TeS: Target temperature of Te (Varies depending on Te setting, operating frequency, etc.)
Heating
Controls compressor capacity to adjust Tc to achieve target value (TcS).
1. VRT control (default)
When the indoor temperature approaches the set temperature in all indoor units and the
required capacity decreases, TcS is automatically decreased to adjust the capacity.
2. Constant control
TcS is fixed to the set value.
Tc setting
Tc: High pressure equivalent saturation temperature
TcS: Target temperature of Tc (Varies depending on Tc setting, operating frequency, etc.)
Branch Selector unit actuator
Normal cooling
Normal simultaneous cooling/heating
Normal heating
Cooling
Heating
Electronic
expansion
valve (EVSC)
Y1E
Thermostat ON
0 pulse
0 pulse
Subcooling degree
control
0 pulse
Non-operating
0 pulse
0 pulse
0 pulse
0 pulse
Thermostat OFF
0 pulse
0 pulse
0 pulse
0 pulse
Electronic
expansion
valve (EVH)
Y2E
Thermostat ON
6,000 pulse
0 pulse
6,000 pulse
6,000 pulse
Non-operating
6,000 pulse
0 pulse
6,000 pulse
6,000 pulse
Thermostat OFF
6,000 pulse
0 pulse
6,000 pulse
6,000 pulse
Electronic
expansion
valve (EVL)
Y3E
Thermostat ON
6,000 pulse
6,000 pulse
0 pulse
0 pulse
Non-operating
6,000 pulse
6,000 pulse
0 pulse
0 pulse
Thermostat OFF
6,000 pulse
6,000 pulse
0 pulse
0 pulse
L
M
H
3°C
(37.4°F)
6°C
(42.8°F)
7°C
(44.6°F)
8°C
(46.4°F)
9°C
(48.2°F)
10°C
(50.0°F)
11°C
(51.8°F)
L
M
H
41°C
(105.8°F)
42°C
(107.6°F)
43°C
(109.4°F)
44°C
(111.2°F)
45°C
(113.0°F)
46°C
(114.8°F)
48°C
(118.4°F)
Содержание VRV EMERION REYQ-AATJA
Страница 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA B 208 230 V REYQ AAYDA B 460 V SiUS372201EB...
Страница 458: ...Check SiUS372201EB 451 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 457 CHECK 8 Refer to page 458...
Страница 490: ...Wiring Diagrams SiUS372201EB 483 Part 7 Appendix 1 2 2 Multi Branch Selector Unit Standard Series BS4Q54TVJ 3D089123B...
Страница 492: ...Wiring Diagrams SiUS372201EB 485 Part 7 Appendix BS6 8Q54TVJ 2D089122B...
Страница 493: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 486 BS10 12Q54TVJ 2D089121B...
Страница 499: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 492 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 500: ...Wiring Diagrams SiUS372201EB 493 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 501: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 494 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 505: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 498 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 506: ...Wiring Diagrams SiUS372201EB 499 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 507: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 500 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 509: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 502 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 513: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 506 FXHQ12 24 36MVJU 3D048116C...
Страница 514: ...Wiring Diagrams SiUS372201EB 507 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 521: ...SiUS372201EB Wiring Diagrams Part 7 Appendix 514 VAM1200GVJU 3D073270D...