Refrigerant Circuit (Piping Diagrams)
SiUS341802EC
37
Part 2 Refrigerant Circuit
1. Refrigerant Circuit (Piping Diagrams)
1.1 Outdoor Unit
No. in
piping
diagram
Electric
symbol
Name
Function
(1)
M1C
Compressor
Compressor is operated in multi-steps according to Te and Tc.
(2)
M1F
M2F
Fan motor
Because the system is an air heat exchange type, the fan rotation speed is
varied by using inverter.
(3)
Y1E
Electronic expansion valve
(Heat exchanger upper)
While in heating, PI control is applied to keep the outlet superheating degree
of air heat exchanger constant.
(4)
Y2E
Electronic expansion valve
(Subcooling heat exchanger)
PI control is applied to keep the outlet superheating degree of subcooling heat
exchanger constant.
(5)
Y3E
Electronic expansion valve
(Heat exchanger lower)
While in heating, PI control is applied to keep the outlet superheating degree
of air heat exchanger constant.
(6)
Y4E
Electronic expansion valve
(Subcooling injection)
Used to control compressor injection.
(7)
Y5E
Electronic expansion valve
(Refrigerant cooling)
Used to control the refrigerant amount to cool the diode bridge and power
module of the inverter PCB.
(8)
Y6E
Electronic expansion valve
(Leak detection)
Used to detect refrigerant leakage.
(9)
Y7E
Electronic expansion valve
(Receiver gas purge)
Used to collect the refrigerant to receiver.
(10)
Y1S
Solenoid valve
(Oil separator oil return)
Used to return oil from the oil separator to the compressor.
(11)
Y2S
Solenoid valve (Hot gas bypass) Used to flow discharge gas to the compressor inlet.
(12)
Y3S
Solenoid valve (Liquid shutoff)
Used to shut off liquid refrigerant flow to the receiver.
(13)
Y4S
Four way valve
(HP/LP gas pipe)
Used to switch dual pressure gas pipe to high pressure or low pressure.
(14)
Y5S
Four way valve
(Heat exchanger lower)
Used to switch outdoor unit heat exchanger to evaporator or condenser.
(15)
Y6S
Four way valve
(Heat exchanger upper)
(16)
Y7S
Solenoid valve
(Accumulator oil return)
Used to return oil from the accumulator to the compressor.
(17)
S1NPH High pressure sensor
Used to detect the high pressure.
(18)
S1NPL Low pressure sensor
Used to detect the low pressure.
(19)
S1PH High pressure switch
(For compressor)
This functions when pressure increases to stop operation and avoid high
pressure increase in the fault operation.
(20)
—
Pressure regulating valve
(Liquid pipe)
This is used when pressure increases, to prevent any damage on
components caused by pressure increase in transport or storage.
(21)
—
Subcooling heat exchanger
Apply subcooling to liquid refrigerant.
(22)
—
Capillary tube
Used to return the refrigerating oil separated through the oil separator to the
compressor.
(23)
R1T
Thermistor (Outdoor air)
Used to detect outdoor air temperature, correct discharge pipe temperature
and others.
(24)
R21T Thermistor (M1C discharge)
Used to detect discharge pipe temperature.
(25)
R3T
Thermistor
(Receiver inlet)
Used to detect liquid pipe temperature of receiver inlet.
(26)
R4T
Thermistor
(Heat exchanger liquid upper)
This detects temperature of liquid pipe for air heat exchanger.
(27)
R5T
Thermistor
(Heat exchanger liquid lower)
(28)
R6T
Thermistor (Subcooling gas)
This detects temperature of gas pipe for subcooling heat exchanger.
(29)
R7T
Thermistor (Subcooling liquid)
This detects temperature of liquid pipe for subcooling heat exchanger.
(30)
R8T
Thermistor
(Heat exchanger gas upper)
This detects temperature of gas pipe for air heat exchanger.
(31)
R9T
Thermistor
(Heat exchanger gas lower)
(32)
R10T Thermistor (Suction)
Used to detect suction pipe temperature.
Содержание VRV Aurora RXLQ-TATJU Series
Страница 376: ...Check SiUS341802EC 369 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 378 CHECK 8 Refer to page 379...
Страница 405: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 398 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU RXLQ72TATJA 2D112580C...
Страница 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Страница 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Страница 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Страница 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 418: ...Wiring Diagrams SiUS341802EC 411 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 427: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 420 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 429: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 422 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Страница 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 441: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 434 VAM1200GVJU 3D073270D...