Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
176
2.3 Operating the BS Buttons and DIP Switches on the PCB
Operating the BS
buttons
By operating the BS buttons it is possible to:
Perform special actions (test operation, etc.).
Perform field settings (demand operation, low noise, etc.).
Below procedure explains how to operate the BS buttons to reach the required mode in the menu,
select the correct setting and modify the value of the setting. This procedure can be used any time
special settings and regular field setting are discussed in this manual.
Setting definition: [A-B]
C
A: mode
B: setting
C: setting value
A, B and C are numerical values for field settings. Parameter C has to be defined. It can be a
chosen from a set (0, 1, 2, 3, 4, 5,…) or regarded as an ON/OFF (1 or 0) depending on the
contents. This is informed when the field setting is explained.
Functions of the BS button switches which are located on the outdoor unit PCB (A1P)
Turn ON the power supply of the outdoor unit and all indoor units.
When the communication between indoor units and outdoor unit(s) is established and normal, the
segment indication state will be as below (default situation when shipped from factory).
When turning ON the power supply, the display blinks ON and OFF. First checks of the power
supply are executed (1 - 2 minutes).
When no trouble occurs: lighted as indicated (8~10 minutes).
Ready for operation: blank display indication as indicated.
Segment display indications:
When above situation cannot be confirmed after 12 minutes, the error code can be checked on the
indoor unit user interface and the outdoor unit segment display. Solve the error code accordingly.
The communication wiring should be checked at first.
INFORMATION During special operation (e.g., test operation, etc.) or when an error
happened, information will contain letters and numerical values.
Off
Blinking
On
INFORMATION Be sure to turn the power on at least 6 hours before operation in
order to have power running to the crankcase heater.
Содержание VRV Aurora RXLQ-TATJU Series
Страница 376: ...Check SiUS341802EC 369 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 378 CHECK 8 Refer to page 379...
Страница 405: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 398 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU RXLQ72TATJA 2D112580C...
Страница 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Страница 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Страница 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Страница 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 418: ...Wiring Diagrams SiUS341802EC 411 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 427: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 420 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 429: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 422 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Страница 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 441: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 434 VAM1200GVJU 3D073270D...