background image

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

10

20

30

40

50

60

70

80

90

15

25

35

45

55

65

75

85

95

100

m (kg)

A

min

 (m

2

)

(b)

(d)

(a)

(c)

m (kg)

A

min

 (m

2

)

m (kg)

A

min

 (m

2

)

m (kg)

A

min

 (m

2

)

(a) 

Ceiling-mounted unit 

(c) 

Other floors

(b) 

Wall-mounted unit 

(d) 

Lowest underground floor

23

12.7

(c) 

/ 7.7

(d)

24

13.1

(c) 

/ 8.1

(d)

25

13.4

(c) 

/ 8.4

(d)

26

13.7

(c) 

/ 8.7

(d)

27

14.1

(c) 

/ 9.1

(d)

10

3.9

(a) 

/ 3.3

(b) 

/ 6.5

(c)

28

14.4

(c) 

/ 9.4

(d)

11

4.1

(a) 

/ 3.7

(b) 

/ 7.2

(c)

29

14.7

(c) 

/ 9.7

(d)

12

4.3

(a) 

/ 4.0

(b) 

/ 7.9

(c)

30

15.1

(c) 

/ 10.1

(d)

13

4.5

(a) 

/ 4.3

(b) 

/ 8.6

(c)

31

15.4

(c) 

/ 10.4

(d)

14

4.7

(a)(b) 

/ 9.3

(c)

32

15.8

(c) 

/ 10.8

(d)

15

5.0

(a)(b) 

/ 10.0

(c)

33

16.1

(c) 

/ 11.1

(d)

16

10.4

(c) 

/ 5.4

(d)

34

16.4

(c) 

/ 11.4

(d)

17

10.7

(c) 

/ 5.7

(d)

35

16.8

(c) 

/ 11.8

(d)

18

11.0

(c) 

/ 6

(d)

36

17.1

(c) 

/ 12.1

(d)

19

11.4

(c) 

/ 6.4

(d)

37

17.4

(c) 

/ 12.4

(d)

20

11.7

(c) 

/ 6.7

(d)

38

17.8

(c) 

/ 12.8

(d)

21

12.0

(c) 

/ 7

(d)

22

12.4

(c) 

/ 7.4

(d)

90

35.3

(c) 

/ 30.3

(d)

91

35.7

(c) 

/ 30.7

(d)

92

36.0

(c) 

/ 31.0

(d)

93

36.4

(c) 

/ 31.4

(d)

94

36.7

(c) 

/ 31.7

(d)

95

37.0

(c) 

/ 32.0

(d)

96

37.4

(c) 

/ 32.4

(d)

97

37.7

(c) 

/ 32.7

(d)

98

38.0

(c) 

/ 33.0

(d)

99

38.4

(c) 

/ 33.4

(d)

100

38.7

(c) 

/ 33.7

(d)

63

26.2

(c) 

/ 21.2

(d)

64

26.6

(c) 

/ 21.6

(d)

65

26.9

(c) 

/ 21.9

(d)

66

27.2

(c) 

/ 22.2

(d)

67

27.6

(c) 

/ 22.6

(d)

68

27.9

(c)v

/ 22.9

(d)

69

28.3

(c) 

/ 23.3

(d)

72

29.3

(c) 

/ 24.3

(d)

55

23.5

(c) 

/ 18.5

(d)

73

29.6

(c) 

/ 24.6

(d)

56

23.9

(c) 

/ 18.9

(d)

74

29.9

(c) 

/ 24.9

(d)

57

24.2

(c) 

/ 19.2

(d)

75

30.3

(c) 

/ 25.3

(d)

58

24.5

(c) 

/ 19.5

(d)

76

30.6

(c) 

/ 25.6

(d)

59

24.9

(c) 

/ 19.9

(d)

77

31.0

(c) 

/ 26.0

(d)

60

25.2

(c) 

/ 20.2

(d)

78

31.3

(c) 

/ 26.3

(d)

61

25.5

(c) 

/ 20.5

(d)

79

31.6

(c) 

/ 26.6

(d)

62

25.9

(c) 

/ 20.9

(d)

80

32.0

(c) 

/ 27.0

(d)

70

28.6

(c) 

/ 23.6

(d)

71

28.9

(c) 

/ 23.9

(d)

81

32.3

(c) 

/ 27.3

(d)

82

32.6

(c) 

/ 27.6

(d)

83

33.0

(c) 

/ 28.0

(d)

84

33.3

(c) 

/ 28.3

(d)

85

33.7

(c) 

/ 28.7

(d)

86

34.0

(c) 

/ 29.0

(d)

87

34.3

(c) 

/ 29.3

(d)

88

34.7

(c) 

/ 29.7

(d)

89

35.0

(c) 

/ 30.0

(d)

51

22.2

(c) 

/ 17.2

(d)

52

22.5

(c) 

/ 17.5

(d)

53

22.8

(c) 

/ 17.8

(d)

54

23.2

(c) 

/ 18.2

(d)

39

18.1

(c) 

/ 13.1

(d)

40

18.5

(c) 

/ 13.5

(d)

41

18.8

(c) 

/ 13.8

(d)

42

19.1

(c) 

/ 14.1

(d)

43

19.5

(c) 

/ 14.5

(d)

44

19.8

(c) 

/ 14.8

(d)

45

20.1

(c) 

/ 15.1

(d)

46

20.5

(c) 

/ 15.5

(d)

47

20.8

(c) 

/ 15.8

(d)

48

21.2

(c) 

/ 16.2

(d)

49

21.5

(c) 

/ 16.5

(d)

50

21.8

(c) 

/ 16.8

(d)

4

Содержание VRV 5-S Series

Страница 1: ...llation and operation manual VRV 5 S system air conditioner English Installation and operation manual VRV 5 S system air conditioner RXYSA4A7V1B RXYSA5A7V1B RXYSA6A7V1B RXYSA4A7Y1B RXYSA5A7Y1B RXYSA6A...

Страница 2: ...HD HU 200 1000 1000 500 HD HU A B C 200 1 300 1000 A B C E 200 1 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 250 1500 300 1500 B D E HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 50...

Страница 3: ...30 7 d 92 36 0 c 31 0 d 93 36 4 c 31 4 d 94 36 7 c 31 7 d 95 37 0 c 32 0 d 96 37 4 c 32 4 d 97 37 7 c 32 7 d 98 38 0 c 33 0 d 99 38 4 c 33 4 d 100 38 7 c 33 7 d 63 26 2 c 21 2 d 64 26 6 c 21 6 d 65 26...

Страница 4: ...1 12 13 14 15 16 17 Direktiver med senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je i...

Страница 5: ...vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota...

Страница 6: ...ioners Indoor unit outdoor unit 21 8 2 11 Symptom Noise of air conditioners Outdoor unit 21 8 2 12 Symptom Dust comes out of the unit 21 8 2 13 Symptom The units can give off odours 21 8 2 14 Symptom...

Страница 7: ...rope com support and manuals product information Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer The original documentation is written...

Страница 8: ...nce with the instructions from this manual See 15 Electrical installation 431 WARNING ALWAYS use multicore cable for power supply cables WARNING If the power supply has a missing or wrong N phase equi...

Страница 9: ...se potential sources of ignition in searching for or detection of refrigerant leaks NOTICE Do NOT re use joints which have been used already Joints made in installation between parts of refrigerant sy...

Страница 10: ...ecautions it is mandatory to install one of the following devices at a location with 24 hour monitoring a supervisor remote controller or an iTM with external alarm via WAGO module Note The remote con...

Страница 11: ...or room 2 1 3 To determine the charge limitations 1 Determine the area of the smallest room in order to derive the total refrigerant charge limit in the system The room area can be determined by proje...

Страница 12: ...for room with the smallest area on the lowest underground floor The maximum allowable charge has to be assessed for the room with the smallest room area in both the lowest underground floor and the o...

Страница 13: ...h c to check the maximum allowed charge for a room of 16 m with a ceiling mounted unit 10 4 kg Use graph d to check the maximum allowed charge for the smallest room 28 m of the lowest underground floo...

Страница 14: ...must be done by an authorized installer and must comply with applicable legislation Units must be treated at a specialized treatment facility for reuse recycling and recovery By ensuring this product...

Страница 15: ...4 About the system The VRV 5 S uses R32 refrigerant which is rated as A2L and is mildly flammable For compliance with the requirements for enhanced tightness refrigerating systems and IEC60335 2 40 th...

Страница 16: ...may stop immediately This is not a malfunction 6 2 3 About the heating operation It may take longer to reach the set temperature for general heating operation than for cooling operation The following...

Страница 17: ...g NOTICE Do not turn off power immediately after the unit stops but wait for at least 5 minutes 6 3 3 To use the dry program WITH cool heat changeover remote control switch To start 1 Select cooling o...

Страница 18: ...e displays of other user interfaces show change over under centralised control 7 Maintenance and service NOTICE Never inspect or service the unit by yourself Ask a qualified service person to perform...

Страница 19: ...leshooting If one of the following malfunctions occur take the measures shown below and contact your dealer WARNING Stop operation and shut off the power if anything unusual occurs burning smells etc...

Страница 20: ...r malfunction Discharge temperature sensor malfunction outdoor Suction temperature sensor malfunction outdoor De icing temperature sensor malfunction outdoor Liquid temperature sensor after subcool HE...

Страница 21: ...tween the units causing them to stop Operation automatically restarts when the noise ceases 8 2 9 Symptom Noise of air conditioners Indoor unit A zeen sound is heard immediately after the power supply...

Страница 22: ...ecycling and recovery For the installer 11 About the box 11 1 Outdoor unit 11 1 1 To unpack the outdoor unit 2 1 11 1 2 To handle the outdoor unit CAUTION To avoid injury do NOT touch the air inlet or...

Страница 23: ...sound pressure level is less than 70 dBA CAUTION Appliance NOT accessible to the general public install it in a secured area protected from easy access This unit is suitable for installation in a comm...

Страница 24: ...l the outdoor unit 4 M12 12 3 3 To provide drainage INFORMATION If necessary you can use a drain pan field supply to prevent drain water from dripping NOTICE If the unit CANNOT be installed fully leve...

Страница 25: ...the piping size Determine the proper size using the following tables and reference figure only for indication A B 1 B 2 C 1 C 2 C 3 C 4 1 3 1 3 2 3 3 3 4 VRV DX 2 2 2 1 Outdoor unit 2 Refrigerant bra...

Страница 26: ...ollowing table in accordance with the total capacity of all the indoor units connected below the refnet header Indoor unit capacity index Refrigerant branch kit 182 KHRQ22M29H INFORMATION Maximum 8 br...

Страница 27: ...sing electrical wiring through the knockout holes wrap the wiring with protective tape to prevent damage 3 Do the following Connect the accessory liquid pipe a to the liquid stop valve brazing Connect...

Страница 28: ...test solution from your wholesaler Do not use soap water which may cause cracking of flare nuts soap water may contain salt which absorbs moisture that will freeze when the piping gets cold and or le...

Страница 29: ...re shall be taken not to overfill the refrigerating system NOTICE Prior to charging the system it shall be pressure tested with the appropriate purging gas The system shall be leak tested on completio...

Страница 30: ...s 437 Result The unit will start operation INFORMATION The manual refrigerant charge operation will automatically stop within 30 minutes If charging is not completed after 30 minutes perform the addit...

Страница 31: ...iring regulations WARNING ALWAYS use multicore cable for power supply cables 15 1 About electrical compliance Equipment complying with EN IEC 61000 3 12 provided that the short circuit power Ssc is gr...

Страница 32: ...th leakage circuit breaker b Fuse c Power supply cable 4 Fix the cables power supply and interconnection cable with a cable tie to the stop valve attachment plate and route the wiring according to the...

Страница 33: ...to SVS output device Specifications of the SVS output Maximum voltage 40 VDC Maximum current 0 025 A Polarity of terminal 1 Polarity of terminal 2 It is mandatory to use a surge killer to protect the...

Страница 34: ...ed above the indoor unit cover the stop valves f see above with sealing material to prevent condensed water on the stop valves from moving to the indoor unit NOTICE Any exposed piping might cause cond...

Страница 35: ...e also 17 1 4 To access mode 1 or 2 436 17 1 5 To use mode 1 436 17 1 6 To use mode 2 436 17 1 7 Mode 1 Monitoring settings 436 17 1 8 Mode 2 Field settings 437 17 1 2 To access the field setting comp...

Страница 36: ...atus of the unit What How Changing and accessing the setting in mode 1 Once mode 1 is selected push BS1 one time you can select the wanted setting It is done by pushing BS2 Accessing the selected sett...

Страница 37: ...remote controller connected to the system 1 Supervisor remote controller connected to system 18 Commissioning NOTICE General commissioning checklist Next to the commissioning instructions in this cha...

Страница 38: ...ctions for equipment using R32 refrigerant 49 Field settings Make sure all field settings you want are set See 17 1 Making field settings 434 Installation date and field setting Be sure to keep a reco...

Страница 39: ...display and on the user interface of the indoor unit 19 1 1 Error codes Overview In case other error codes appear contact your dealer Main code Cause Solution SVEO a SVS b The R32 sensor in one of the...

Страница 40: ...ly voltage Check if power supply is within range Insufficient supply voltage Check if the supply voltage is supplied properly Malfunction code System test run not yet executed system operation not pos...

Страница 41: ...0 11 and audible alarm and red warning signal is generated from this remote controller The unit number is displayed on this remote controller k Error code U9 02 is displayed on this remote controller...

Страница 42: ...s walls baffle plates E Obstacle roof a b c d e Minimum service space between the unit and obstacles A B C D and E eB Maximum distance between the unit and the edge of obstacle E in the direction of o...

Страница 43: ...rheat g One way valve R7T Thermistor heat exchanger h Pressure relief valve R10T Thermistor fin i PCB cooling R21T Thermistor discharge j Double tube heat exchanger k Distributor Refrigerant flow l He...

Страница 44: ...PTC thermistor S1NPH High pressure sensor S1NPL Low pressure sensor S1PH High pressure switch S1S Air control switch option S2S Cool heat selector switch option SEG A1P 7 segment display SFB Mechanic...

Страница 45: ...itch option SEG A1P 7 segment display SFB Mechanical ventilation error input field supply V D Diode module V1R V2R A1P IGBT power module V3R A1P Diode module X A PCB connector X M Terminal strip X Y C...

Страница 46: ......

Страница 47: ......

Страница 48: ...4P600329 1A 2020 01 Copyright 2020 Daikin 4P600329 1 A 0000000X Verantwortung f r Energie und Umwelt...

Отзывы: