8 Troubleshooting

Installation and operation manual

14

RXYSA4~6A7V/Y1B

VRV 5-S system air conditioner

4P600329-1E – 2023.02

Malfunction

Measure

The system operates
but cooling or heating
is insufficient.

▪ Check  if  air  inlet  or  outlet  of  outdoor  or

indoor  unit  is  not  blocked  by  obstacles.
Remove  any  obstacles  and  make  sure
the air can flow freely.

▪ Check if the air filter is not clogged (refer

to  "Maintenance"  in  the  indoor  unit
manual).

▪ Check the temperature setting.

▪ Check the fan speed setting on your user

interface.

▪ Check for open doors or windows. Close

doors and windows to prevent wind from
coming in.

▪ Check if there are too many occupants in

the room during cooling operation. Check
if  the  heat  source  of  the  room  is
excessive.

▪ Check  if  direct  sunlight  enters  the  room.

Use curtains or blinds.

▪ Check if the air flow angle is proper.

If  after  checking  all  above  items,  it  is  impossible  to  fix  the  problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).

8.1

Error codes: Overview

In case a malfunction code appears on the indoor unit user interface
display,  contact  your  installer  and  inform  the  malfunction  code,  the
unit  type,  and  serial  number  (you  can  find  this  information  on  the
nameplate of the unit).

For  your  reference,  a  list  with  malfunction  codes  is  provided.  You
can, depending on the level of the malfunction code, reset the code
by pushing the ON/OFF button. If not, ask your installer for advice.

Main code

Contents

External protection device was activated

The R32 sensor in one of the indoor units has
detected a refrigerant leak

(a)

/

Safety system error (leak detection)

(a)

EEPROM failure (indoor)

Drain system malfunction (indoor)

Fan motor malfunction (indoor)

Swing flap motor malfunction (indoor)

Expansion valve malfunction (indoor)

Drain malfunction (indoor unit)

Filter dust chamber malfunction (indoor)

Capacity setting malfunction (indoor)

Transmission malfunction between main PCB and sub
PCB (indoor)

Heat exchanger thermistor malfunction (indoor; liquid)

Heat exchanger thermistor malfunction (indoor; gas)

Suction air thermistor malfunction (indoor)

Discharge air thermistor malfunction (indoor)

Movement detector or floor temperature sensor
malfunction (indoor)

R32 sensor malfunction in one of the indoor units

(a)

R32 sensor end of lifetime in one of the indoor units

(a)

R32 sensor 6 months before end of lifetime in one of
the indoor units

(a)

Main code

Contents

Waiting for R32 sensor replacement confirmation from
one of the indoor units

(a)

User interface thermistor malfunction (indoor)

PCB malfunction (outdoor)

High pressure switch was activated

Low pressure malfunction (outdoor)

Compressor lock detection (outdoor)

Fan motor malfunction (outdoor)

Electronic expansion valve malfunction (outdoor)

Discharge temperature malfunction (outdoor)

Abnormal suction temperature (outdoor)

Refrigerant overcharge detection

High pressure switch malfunction

Fan motor trouble (outdoor)

Ambient temperature sensor malfunction (outdoor)

Pressure sensor malfunction

Current sensor malfunction

Discharge temperature sensor malfunction (outdoor)

Suction temperature sensor malfunction (outdoor)

De-icing temperature sensor malfunction (outdoor)

Liquid temperature sensor (after subcool HE)
malfunction (outdoor)

Gas temperature sensor (after subcool HE)
malfunction (outdoor)

High pressure sensor malfunction (S1NPH)

Low pressure sensor malfunction (S1NPL)

INV PCB abnormal

Fin temperature abnormal

Inverter PCB faulty

Compressor over current detected

Compressor lock (startup)

Shut-off PCB transmission trouble or disconnection

INV unbalanced power supply voltage

Fin thermistor malfunction

Capacity setting malfunction (outdoor)

Abnormal low pressure drop, faulty expansion valve

INV voltage power shortage

System test run not yet executed

Faulty wiring indoor/outdoor

Abnormal user interface - indoor communication

Abnormal main-sub user interface communication

System mismatch. Wrong type of indoor units
combined. Indoor unit malfunction.

Connection malfunction over indoor units or type
mismatch

System lock

Back-up PCB error

External ventilation input error

Centralised address duplication

Malfunction in communication centralised control
device - indoor unit

Auto address malfunction (inconsistency)

Auto address malfunction (inconsistency)

(a)

The error code is only shown on the user interface of the indoor
unit where the error occurs.

Содержание VRV 5-S RXYSA4A7V1B

Страница 1: ...llation and operation manual VRV 5 S system air conditioner English Installation and operation manual VRV 5 S system air conditioner RXYSA4A7V1B RXYSA5A7V1B RXYSA6A7V1B RXYSA4A7Y1B RXYSA5A7Y1B RXYSA6A...

Страница 2: ...HD HU 200 1000 1000 500 HD HU A B C 200 1 300 1000 A B C E 200 1 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 250 1500 300 1500 B D E HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 50...

Страница 3: ...1 0 21 5 22 0 22 6 23 1 23 6 24 2 24 7 25 3 25 8 26 3 26 9 27 4 27 9 4 6 5 5 6 0 6 5 6 9 7 2 7 6 7 9 8 2 8 6 9 2 9 8 10 4 11 1 11 7 12 3 12 9 13 5 14 1 14 7 15 4 16 0 16 6 17 2 17 8 18 4 19 0 19 6 20...

Страница 4: ...urs 15 8 2 14 Symptom The outdoor unit fan does not spin 16 8 2 15 Symptom The compressor in the outdoor unit does not stop after a short heating operation 16 8 2 16 Symptom The inside of an outdoor u...

Страница 5: ...data Detailed step by step instructions and background information for basic and advanced usage Format Digital files on https www daikin eu Use the search function to find your model Latest revisions...

Страница 6: ...WARNING If the power supply has a missing or wrong N phase equipment might break down Establish proper earthing Do NOT earth the unit to a utility pipe surge absorber or telephone earth Incomplete ea...

Страница 7: ...d excessive vibration or pulsation to refrigeration piping Protect the protection devices piping and fittings as much as possible against adverse environmental effects Provide space for expansion and...

Страница 8: ...vironment and human health 3 2 Instructions for safe operation CAUTION NEVER touch the internal parts of the controller Do NOT remove the front panel Some parts inside are dangerous to touch and appli...

Страница 9: ...ON NEVER expose little children plants or animals directly to the airflow WARNING The unit is equipped with a refrigerant leak detection system for safety To be effective the unit MUST be electrically...

Страница 10: ...r interface whose display shows change over under centralised control refer to installation and operation manual of the user interface When the display change over under centralised control flashes re...

Страница 11: ...to operation if the room temperature is low 20 C 6 3 2 To use the dry program WITHOUT cool heat changeover remote control switch To start 1 Press the operation mode selector button on the user interfa...

Страница 12: ...the master user interface can select heating or cooling mode 6 5 2 To designate the master user interface 1 Press the operation mode selector button of the current master user interface for 4 seconds...

Страница 13: ...l name of the unit The manufacturing number stated on the nameplate of the unit The installation date The symptoms or malfunction and details of the defect WARNING Do NOT modify disassemble remove rei...

Страница 14: ...mistor malfunction indoor gas Suction air thermistor malfunction indoor Discharge air thermistor malfunction indoor Movement detector or floor temperature sensor malfunction indoor R32 sensor malfunct...

Страница 15: ...g cooling operation If the interior of an indoor unit is extremely contaminated the temperature distribution inside a room becomes uneven It is necessary to clean the interior of the indoor unit Ask y...

Страница 16: ...es hydrofluorocarbon Contact your dealer when discarding this unit It is required by law to collect transport and discard the refrigerant in accordance with the hydrofluorocarbon collection and destru...

Страница 17: ...ected failure or disconnection of the R32 sensor located in the indoor unit For more information about the SVS output see 16 4 To connect the external outputs 432 Indoor unit installation NOTICE If on...

Страница 18: ...t of the remote controller is not sufficient to guarantee the 15 dB difference This alarm can be connected to the SVS output channel of the outdoor unit or to the optional output PCB of the indoor uni...

Страница 19: ...6 a b b d a b b b d Group control is allowed up to a maximum of 5 indoor units connected to different ports or connected to the same port At least one R32 safety system compatible remote controller s...

Страница 20: ...Lowest underground floor Lowest underground floor c Effective installation height Effective installation height Determine the value for both the lowest underground floor AND the other floors The tota...

Страница 21: ...System charge kg 16 0 Judgement a b b b b B D C A a Outdoor unit b Indoor unit A B C D Room A B C D Example 2 Room A B C D Area m 10 20 10 20 Installation height m 3 0 2 2 3 0 2 2 Lowest underground f...

Страница 22: ...allation site WARNING The appliance shall be stored in a room without continuously operating ignition sources example open flames an operating gas appliance or an operating electric heater 13 1 1 Inst...

Страница 23: ...nit 13 3 1 To provide the installation structure Prepare 4 sets of anchor bolts nuts and washers field supply as follows mm 7 5 8 150 4 8 0 4 9 0 4 8 5 4 M12 a a Make sure not to cover the drain holes...

Страница 24: ...cated in the following illustration field supply 2 Place the 2 cables over the outdoor unit 3 Insert a rubber sheet between the cables and the outdoor unit to prevent the cables from scratching the pa...

Страница 25: ...or unit Use the same diameters as the connections liquid gas on the indoor units The diameters of the indoor units are as follows Indoor unit capacity index Piping outer diameter size mm Gas pipe Liqu...

Страница 26: ...panel Especially for the bottom and side connection be sure to protect the piping with suitable insulation to prevent it from coming into contact with the casing 1 Do the following Remove the service...

Страница 27: ...es either horizontally or vertically Mount the refnet header so that it branches horizontally A B 3 0 a b c d a a Horizontal surface b Refnet joint mounted vertically c Refnet joint mounted horizontal...

Страница 28: ...order to have power running to the crankcase heater and to protect the compressor NOTICE If operation is performed within 12 minutes after the indoor and outdoor units are powered on the compressor w...

Страница 29: ...ng If Then The determined additional refrigerant amount is reached Disconnect the manifold from the liquid line You do not have to perform the Charging refrigerant in manual additional refrigerant cha...

Страница 30: ...Potential NOTICE Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicated both in weight and CO2 equivalent Formula to calculate the quantit...

Страница 31: ...ice 30 mA MUST comply with national wiring regulation a MCA Minimum circuit ampacity Stated values are maximum values see electrical data of combination with indoor units for exact values 16 3 To conn...

Страница 32: ...sh c Nut d Frame e Tube 8 Route the cables out of the unit WARNING Avoid sharp edges when routing cables to the rear Make sure to route the cables through the left side of the accumulator foot when pa...

Страница 33: ...75 mm For the SVEO connection it is recommended to use a shielded cable The cable shield must be earthed at the marked earthing point that is located on the support frame of the terminal Y1 V1 c a b c...

Страница 34: ...ich can withstand a temperature of 120 C for gas piping Reinforce the insulation on the refrigerant piping according to the installation environment Ambient temperature Humidity Minimum thickness 30 C...

Страница 35: ...ue and changing the current field setting value is possible In general normal operation can be resumed without special intervention after changing field settings Some field settings are used for speci...

Страница 36: ...on Access Action Mode 1 Push BS1 one time 7 segment display indication changes to Push BS1 one more time to return to the default situation Mode 2 Push BS1 for at least 5 seconds 7 segment display ind...

Страница 37: ...Note For an ESP level higher than 45 Pa level 0 is kept for reliability of the fan motor 2 18 Description 0 default Auto setting at commissioning mode and stand by mode 1 Auto setting at commissioning...

Страница 38: ...ox and the inside of the unit for loose connections or damaged electrical components Pipe size and pipe insulation Be sure that correct pipe sizes are installed and that the insulation work is properl...

Страница 39: ...rmality When the test operation is fully completed normal operation will be possible after 5 minutes 19 6 Correcting after abnormal completion of the test run The test operation is only completed if t...

Страница 40: ...ring any excessive refrigerant with a refrigerant recovery machine Ambient temperature sensor malfunction R1T A1P X18A Check connection on PCB or actuator Discharge temperature sensor malfunction R21T...

Страница 41: ...ce manual for more information WARNING The unit is equipped with a refrigerant leak detection system for safety To be effective the unit MUST be electrically powered at all times after installation ex...

Страница 42: ...nimum service space between the unit and obstacles A B C D and E eB Maximum distance between the unit and the edge of obstacle E in the direction of obstacle B eD Maximum distance between the unit and...

Страница 43: ...ributor Refrigerant flow l Heat exchanger Cooling m Accumulator Heating n Muffler o Capillary tube p Compressor accumulator M1C Compressor M1F Fan motor HPS A High pressure switch automatic reset HPS...

Страница 44: ...VT Y3E Electronic expansion valve main EVM2 Y4E Electronic expansion valve EVL Y5E Electronic expansion valve EVSL Y6E Electronic expansion valve EVSG Y1S Solenoid valve 4 way valve Y3S Error operatio...

Страница 45: ...n EVM1 Y2E Electronic expansion valve EVT Y3E Electronic expansion valve main EVM2 Y4E Electronic expansion valve EVL Y5E Electronic expansion valve EVSL Y6E Electronic expansion valve EVSG Y1S Soleno...

Страница 46: ......

Страница 47: ......

Страница 48: ...4P600329 1E 2023 02 Copyright 2020 Daikin 4P600329 1 E 0000000 Verantwortung f r Energie und Umwelt...

Отзывы: