17
|
Unit installation
Installer and user reference guide
88
RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P749918-1 – 2023.12
14~20 HP
6×
SW8
NOTICE
When closing the switch box cover, make sure that the sealing material on the lower
back side of the cover is NOT caught and bent towards the inside (see figure below).
a
b
c
d
e
a
Switch box cover
b
Front side
c
Power supply terminal block
d
Sealing material
e
Moisture and dirt could enter
NOT allowed
Allowed
17.3 Mounting the outdoor unit
17.3.1 To provide the installation structure
Make sure the unit is installed level on a sufficiently strong base to prevent
vibration and noise.
NOTICE
▪
When the installation height of the unit needs to be increased, do NOT use stands
to only support the corners.
▪
Stands under the unit must be at least 100 mm wide.
NOTICE
The height of the foundation must at least be 150 mm from the floor. In heavy
snowfall areas, this height should be increased up to the average expected snow
level, depending on the installation place and condition.
≥100 mm
≥100 mm
*
NOT allowed
Allowed (* = preferred installation)
▪
The preferred installation is on a solid longitudinal foundation (steel beam frame
or concrete). The foundation must be larger than the grey marked area.