9.5.4 Shortened maintenance and replacement cycles
Shortening of "maintenance cycle" and "replacement cycle" needs to be
considered in following situations:
The unit is used in locations where:
▪
Heat and humidity fluctuate out of the ordinary.
▪
Power fluctuation is high (voltage, frequency, wave distortion, etc.) (the unit
cannot be used if power fluctuation is outside the allowable range).
▪
Bumps and vibrations are frequent.
▪
Dust, salt, harmful gas or oil mist such as sulphurous acid and hydrogen sulfide
may be present in the air.
▪
The machine is started and stopped frequently or operation time is long (sites
with 24 hour air-conditioning).
Recommended replacement cycle of wear parts
Component
Inspection
cycle
Maintenance cycle
(replacements and/or repairs)
Air filter
1 year
5 years
High efficiency filter
1 year
Fuse
10 years
Crankcase heater
8 years
Pressure containing parts
In case of corrosion, contact
your local dealer.
NOTICE
▪
The table indicates main components. Refer to your maintenance and inspection
contract for more details.
▪
The table indicates recommended intervals of replacement cycles. However, in
order to keep the unit operational as long as possible, maintenance work may be
required sooner. Recommended intervals can be used for appropriate
maintenance design in terms of budgeting maintenance and inspection fees.
Contact your dealer for details.
INFORMATION
Damage due to taking apart or cleaning interiors of units by anyone other than our
authorised dealers may not be included in the warranty.