7
|
Operation
Installer and user reference guide
30
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P687640-1 – 2022.07
In case of
Then
REYA10~28 (multi-use
models)
The indoor unit will continue heating operation at a
reduced level during defrost operation. It will
guarantee a decent comfort level indoor.
REYA8~20 (single-use
models)
The indoor unit will stop fan operation, the
refrigerant cycle will reverse and energy from inside
the building will be used to defrost the outdoor unit
coil.
The indoor unit will indicate defrost operation on the display
.
Hot start
In order to prevent cold air from blowing out of an indoor unit at the start of
heating operation, the indoor fan is automatically stopped. The display of the user
interface shows
. It may take some time before the fan starts. This is not a
malfunction.
INFORMATION
▪
The heating capacity drops when the outside temperature falls. If this happens,
use another heating device together with the unit. (When using together with
appliances that produce open fire, ventilate the room constantly). Do not place
appliances that produce open fire in places exposed to the air flow from the unit
or under the unit.
▪
It takes some time to heat up the room from the time the unit is started since the
unit uses a hot-air circulating system to heat the entire room.
▪
If the hot air rises to the ceiling, leaving the area above the floor cold, we
recommend that you use the circulator (the indoor fan for circulating air).
Contact your dealer for details.
7.3.4 To operate the system
1
Press the operation mode selector button on the user interface several times
and select the operation mode of your choice.
Cooling operation
Heating operation
Fan only operation
2
Press the ON/OFF button on the user interface.
Result:
The operation lamp lights up and the system starts operating.
7.4 Using the dry program
7.4.1 About the dry program
▪
The function of this program is to decrease the humidity in your room with
minimal temperature decrease (minimal room cooling).
▪
The micro computer automatically determines temperature and fan speed
(cannot be set by the user interface).
▪
The system does not go into operation if the room temperature is low (<20°C).