15
|
Piping installation
Installer and user reference guide
75
BS4~12A14AJV1B
VRV 5 branch selector unit
4P695527-1 – 2022.02
Outer diameter (Ø)
Temper grade
Thickness (t)FN
6.4 mm (1/4")
9.5 mm (3/8")
12.7 mm (1/2")
Annealed (O)
≥0.80 mm
t
Ø
15.9 mm (5/8")
Annealed (O)
≥0.99 mm
19.1 mm (3/4")
22.2 mm (7/8")
Half hard (1/2H)
≥0.80 mm
28.6 mm (1 1/8")
Half hard (1/2H)
≥0.99 mm
15.2.3 Refrigerant piping insulation
▪
Use polyethylene foam as insulation material:
-
with a heat transfer rate between 0.041 and 0.052 W/mK (0.035 and
0.045 kcal/mh°C)
-
with a heat resistance of at least 120°C
▪
Insulation thickness
Ambient temperature
Humidity
Minimum thickness
≤30°C
75% to 80% RH
15 mm
>30°C
≥80% RH
20 mm
15.3 Connecting the refrigerant piping
15.3.1 To connect the refrigerant piping
e
e
b
a
d
c
g
h
e
f f
f f
f f
f
a
BS unit
b
Liquid pipe (field supply)
c
HP/LP gas pipe (field supply)
d
Suction gas pipe (field supply)
e
Reducing joints and insulation tubes (accessory)
f
Indoor unit connection set
g
Liquid pipe (field supply)
h
Gas pipe (field supply)