13
|
Special requirements for R32 units
Installer and user reference guide
45
BS4~12A14AJV1B
VRV 5 branch selector unit
4P695527-1 – 2022.02
BS unit
Room area
Required safety measure
1
A=125 m²≥118 m²
No safety measures
2
A=70 m²≥59 m²
External alarm
3
A=15 m²<59 m²
Ventilated enclosure
0
10
20
30
40
50
70
90
110
80
118
59
100
140
150
130
160
5 10
20
30
40
50
25
15
35
45
m [kg]
A
min
[m
2
]
No safety measure
(c)
External alarm
(d)
Ventilated enclosure
(e)
m
Total refrigerant charge in the system [kg]
A
min
Minimum room area [m²]
(a)
All other floors (=All other floors)
(b)
Lowest underground floor (=Lowest underground floor)
(c)
No safety measure (=No safety measure)
(d)
External alarm (=External alarm)
(e)
Ventilated enclosure (=Ventilated enclosure)
13.4 Safety measures
13.4.1 No safety measure
When the room area is sufficiently large, no safety measures are required. This also
includes a BS unit installed in the lowest underground floor.
The duct connection must be replaced with the duct closing plate accessory (see
"14.5.2 To install the duct closing plate"
66]).
BS unit test run
Before BS unit operation, it is required to perform a test run that simulates a
refrigerant leak. See
101] for more details.
Field settings
No safety measure
Code
Description
Value
[2-0]
Cluster indication
0 (default): disable
[2-4]
Safety measures
0: disable
Note:
Some field settings need to be made on all main PCBs (A1P, A2P and A3P) of
the same BS unit. For more information, see
91].
13.4.2 External alarm
Do NOT use the external alarm safety measure in the following cases:
▪
BS unit is installed in the lowest underground floor of a building.
▪
BS unit is installed in in an occupied space where people are restricted in their
movement.