16 Configuration

Installation and operation manual

36

BS4~12A14AJV1B

VRV 5 branch selector unit

4P670163-1 – 2022.02

What

How

Changing and accessing
the setting in mode 1

Once mode 1 is selected (push BS1
one time), you can select the wanted
setting. It is done by pushing BS2.

Accessing the selected setting's value is
done by pushing BS3 one time.

To quit and return to the
initial status

Press BS1.

Example

Checking  the  content  of  parameter  [1‑2]  (to  know  the  software
version).

[Mode-Setting]=Value  in  this  case  defined  as:  Mode=1;  Setting=2;
Value=the value we want to know/monitor:

1

Make  sure  the  7‑segment  display  indication  is  in  the  default
situation (normal operation).

2

Push BS1 one time.

Result: 

Mode 1 is accessed: 

3

Push BS2 two times.

Result: 

Mode 1 setting 2 is addressed: 

4

Push BS3 one time; the value which is returned is the software
version.

Result: 

Mode  1  setting  2  is  addressed  and  selected,  return

value is monitored information

5

To quit mode 1, push BS1 one time.

16.1.6

To use mode 2

Mode 2 is used to set field settings of the BS unit.

What

How

Changing and accessing
the setting in mode 2

Once mode 2 is selected (push BS1 for
more than 5 seconds), you can select
the wanted setting. It is done by pushing
BS2.

Accessing the selected setting's value is
done by pushing BS3 1 time.

To quit and return to the
initial status

Press BS1.

Changing the value of the
selected setting in mode 2

▪ Once  mode  2  is  selected  (push  BS1

for  more  than  5  seconds)  you  can
select  the  wanted  setting.  It  is  done
by pushing BS2.

▪ Accessing the selected setting's value

is done by pushing BS3 1 time.

▪ Now  BS2  is  used  to  select  the

required value of the selected setting.

▪ When  the  required  value  is  selected,

you  can  define  the  change  of  value
by pushing BS3 1 time.

▪ Press  BS3  again  to  start  operation

according to the chosen value.

Example

Checking  the  content  of  parameter  [2‑7]  (to  enable  or  disable  the
ventilated enclosure function).

[Mode‑Setting]=Value in this case is defined as: Mode=2; Setting=7;
Value=the value we want to know/change.

1

Make  sure  the  7‑segment  display  indication  is  in  the  default
situation (normal operation).

2

Push BS1 for more than 5 seconds.

Result: 

Mode 2 is accessed: 

3

Push BS2 seven times.

Result: 

Mode 2 setting 7 is addressed: 

4

Push BS3 1 time; the value which is returned (depending on the
actual field situation), is the status of the setting. In the case of
[2‑7],  the  default  value  is  "1",  which  means  the  ventilated
enclosure function is enabled.

Result: 

Mode  2  setting  7  is  addressed  and  selected,  return

value is the current setting situation.

5

To  change  the  value  of  the  setting,  push  BS2  till  the  required
value  appears  on  the  7‑segment  display  indication.  When
achieved, define the setting value by pushing BS3 one time. To
start  operation  according  to  the  chosen  setting,  confirm  again
by pushing BS3.

6

To quit mode 2, push BS1 one time.

16.1.7

Mode 1: Monitoring settings

[1-0]

Shows the remaining lifetime of the R32 sensor.

The remaining lifetime is displayed in months ranging from 0 to 120.

INFORMATION

The  sensor  has  a  lifetime  of  10  years.  The  user  interface
displays  error  "

CH-22

"  6  months  before  the  end  of  the

sensor  lifetime  and  error  "

CH-23

"  after  the  end  of  the

sensor  lifetime.  For  more  information,  see  the  reference
guide of the user interface and contact your dealer.

16.1.8

Mode 2: Field settings

[2-0]

Setting to define if the BS unit belongs to a cluster or not.

In case the BS unit belongs to a parallel or series cluster, this setting
has  to  be  put  on  "1"  to  enable  it.  See 

"12.3  To  determine  the

required safety measures"

 [

4

 14].

This setting must be made on all main PCB's (A1P, A2P and A3P) of
the BS unit.

[2-0]

Definition

0 (default)

Cluster disabled

1

Cluster enabled

[2-1]

Setting to define the cluster number the BS unit belongs to.

In  case  there  are  multiple  clusters  in  the  system,  all  BS  units
belonging to the same cluster need to have the same cluster number
as value for this setting. BS units belonging to different clusters need
to have a different cluster number.

This setting must be made on all main PCB's (A1P, A2P and A3P) of
the BS unit.

[2-1]

Definition

0 (default)~15

Cluster number

[2-2]

Setting to define the cluster configuration the BS unit belongs to.

This  can  be  either  a  parallel  or  series  cluster.  This  setting  must  be
made  for  all  BS  units  in  the  same  cluster,  and  has  to  be  the  same
value. See 

"12.3 To determine the required safety measures"

 [

4

 14].

This setting must be made on all main PCB's (A1P, A2P and A3P) of
the BS unit.

Содержание VRV 5 BS4A14AJV1B

Страница 1: ...Installation and operation manual VRV 5 branch selector unit English Installation and operation manual VRV 5 branch selector unit BS4A14AJV1B BS6A14AJV1B BS8A14AJV1B BS10A14AJV1B BS12A14AJV1B...

Страница 2: ...measure c External alarm d m kg Amin m All other floors a All other floors a Lowest under ground floor b No safety measure c No safety measure c External alarm d 5 16 15 16 35 207 104 207 6 23 18 23...

Страница 3: ...iai bus eksploatuojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo pred...

Страница 4: ...he products are used in accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the...

Страница 5: ...3 4 3 To install the drain piping 24 13 5 Installing the ventilation ducting 24 13 5 1 To install the ducting field supply 24 13 5 2 To install the duct closing plate 25 13 5 3 To switch the air in an...

Страница 6: ...approved by the manufacturer are used in the duct work WARNING Do NOT install operating ignition sources example open flames an operating gas appliance or an operating electric heater in the duct wor...

Страница 7: ...wer supply cables WARNING If the supply cord is damaged it MUST be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard WARNING Use an all pole disc...

Страница 8: ...enance purposes See 12 3 To determine the required safety measures 4 14 to check if your system meets the R32 safety requirements For the user 3 User safety instructions Always observe the following s...

Страница 9: ...ways have qualified service personnel confirm that the point of leakage has been repaired or corrected before resuming operation WARNING This unit contains electrical and hot parts WARNING Before oper...

Страница 10: ...structions from Daikin and in addition comply with applicable legislation and are performed by qualified persons only In Europe and areas where IEC standards apply EN IEC 60335 2 40 is the applicable...

Страница 11: ...the unit by yourself Ask a qualified service person to perform this work 6 1 Precautions for maintenance and service CAUTION See 3 User safety instructions 48 to acknowledge all related safety instruc...

Страница 12: ...ned malfunctions is evident investigate the system in accordance with the following procedures Malfunction Measure If a refrigerant leak occurs error code Actions will be taken by the system Do NOT tu...

Страница 13: ...it and options 11 1 About combining units and options 11 1 1 Possible options for the BS unit INFORMATION All possible options are mentioned in the option list below For more information about an opti...

Страница 14: ...he outdoor unit For installation of the indoor unit see the installation and operation manual delivered with the indoor unit For compatibility of indoor units see the latest version of the technical d...

Страница 15: ...arm e Ventilated enclosure Ventilated enclosure Use the total amount of refrigerant in the system and the area of the room in which the BS unit is installed to check what is the safety measure that ne...

Страница 16: ...ntrolled number of people are present accessible for persons not familiar with the necessary safety precautions To warn at a supervised location connect a supervisor remote controller to the system Th...

Страница 17: ...hen compared with the pressure of the surroundings The minimum required airflow rate AFROUT is 18 8 m h and the pressure drop generated by the BS unit should lead to a pressure inside the BS unit Pint...

Страница 18: ...parallel BS units are connected to a single extraction fan Each BS unit benefits from a direct airflow path to the extraction fan In case of a refrigerant leak in any BS unit the damper of that BS uni...

Страница 19: ...t run that simulates a refrigerant leak See 17 1 BS unit test run 438 for more details Field settings Multiple BS units in series one extraction fan Code Description Value 2 0 Cluster indication 1 ena...

Страница 20: ...ames an operating gas appliance or an operating electric heater 13 1 1 Installation site requirements of the unit CAUTION Appliance NOT accessible to the general public install it in a secured area pr...

Страница 21: ...length Keep drain piping as short as possible Drain pipe size Keep the pipe size equal to or greater than that of the connecting pipe vinyl pipe of 20 mm nominal diameter and 26 mm outer diameter Bad...

Страница 22: ...lt flow Ducting on both sides B Reversed flow Only ducting on the air outlet side B Reversed flow Ducting on both sides C No extraction ventilation installed 1 To extraction fan or another BS unit 2 F...

Страница 23: ...pension bolt Leave enough space for maneuvering with the unit between the nut and double nut 3 Position the unit by hooking the hanger brackets of the unit around the suspension bolts in between the t...

Страница 24: ...n hose Note Start on the screw part of the metal clamp work your way around the clamp and end overlapping your starting point 5 b a c d a Drain pipe connection attached to the unit b Drain hose access...

Страница 25: ...der the field supply insulation Create an overlap of 50 mm If the entire outlet duct is thermally insulated from the unit to the outside wall the accessory sealing material is not necessary a d e d e...

Страница 26: ...wire Store the screw in a safe place Cut the cable ties that fix the damper wire to the pipe and the one that bundles the damper wire a b b b a Damper wire b Cable ties 8 Remove the damper Remove the...

Страница 27: ...his makes the connection airtight Attach the damper with 4 screws 4 PH2 SW8 3 2 N m a b b b b c 1 2 a Damper wire b Screw c Damper 15 Connect the damper wires a b c 1 PH2 1 7 N m a Connector b Earth w...

Страница 28: ...a b c d BS4A a b b c d BS6 12A a Damper wire b Tie wrap to fix damper wire to piping field supply c Tie wrap to bundle the damper wire field supply d Leftmost wire fixing plate To re install the switc...

Страница 29: ...6 Maximum number of indoor units connected to BS units in refrigerant flow through c 64 14 2 Preparing refrigerant piping 14 2 1 Refrigerant piping requirements NOTICE The piping and other pressure co...

Страница 30: ...erant flow through with another BS unit and unused branch pipes when no indoor unit is connected to that branch pipe port 5 In case of stopper pipes install stopper pipe insulation tubes accessory Add...

Страница 31: ...art from each other Transmission wiring and power supply wiring may cross but may NOT run parallel In order to avoid any electrical interference the distance between both wirings should ALWAYS be at l...

Страница 32: ...e corresponding indoor unit multiple indoor units connected to the same branch the terminals F1 F2 Indoor unit X on the BS unit to the F1 F2 terminals on the first indoor unit Connect the F1 F2 termin...

Страница 33: ...tape e Transmission wiring F1 F2 f Insulation 15 4 To set the DIP switches The DIP switches are located on the PCB s A1P A2P BS6 12A and A3P BS10 12A A1P A2P A3P A B C D E F G H I J K L A B C D E F G...

Страница 34: ...MPLE a FAN output terminal b Relay c Extraction fan power supply d Extraction fan SVS output external alarm The SVS output is a potential free contact on terminal X6M that closes in case a leak is det...

Страница 35: ...Value Example Description Default situation Mode 1 Mode 2 Description Setting 8 in mode 2 Value 4 in mode 2 16 1 4 To access mode 1 or 2 Initialisation default situation NOTICE Be sure to turn ON the...

Страница 36: ...r more than 5 seconds Result Mode 2 is accessed 3 Push BS2 seven times Result Mode 2 setting 7 is addressed 4 Push BS3 1 time the value which is returned depending on the actual field situation is the...

Страница 37: ...on the 7 segment display of the outdoor unit This setting must only be made on the leftmost main PCB A1P of each BS unit 2 6 Commissioning check 0 default Incomplete 1 Completed 2 7 Setting to enable...

Страница 38: ...he BS unit test run The BS unit test run has to be performed on all BS units in the system before the test run of the outdoor unit The BS unit test run has to confirm that the required safety measures...

Страница 39: ...e airflow rate at the air inlet damper of the BS unit Tip Use the duct connection kit EKBSDCK and an anemometer with a funnel to conduct the entire airflow through the anemometer Postrequisite Remove...

Страница 40: ...uring BS unit test run Symptom The damper does not open Possible causes Corrective action Incorrect field settings Check if all field settings are made correctly When in parallel or series configurati...

Страница 41: ...by your local dealer This chapter gives you an overview of the most possible error codes and their descriptions as they appear on the user interface INFORMATION See the service manual for The complet...

Страница 42: ...PTC thermistor Q Insulated gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth leak circuit breaker Q L Overload protector Symbol Meaning Q M Thermo switch Q R Residual current device R R...

Страница 43: ...or for the product Authorised installer Technical skilled person who is qualified to install the product User Person who is owner of the product and or operates the product Applicable legislation All...

Страница 44: ...4P670163 1 2022 02 Copyright 2022 Daikin 4P670163 1 0000000L Verantwortung f r Energie und Umwelt...

Отзывы: