13 Unit installation

Installation and operation manual

20

BS4~12A14AJV1B

VRV 5 branch selector unit

4P670163-1 – 2022.02

12.6

Combinations of safety measures

It is possible to combine BS units with different safety measures (no
safety  measures,  external  alarm  and  ventilated  enclosure)  in  the
same system.

Example

a

b

b

e

f

d

c

a

Outdoor unit

b

BS unit with ventilated enclosure safety measure

c

BS unit without safety measures

d

BS unit with external alarm safety measure

e

Extraction fan

f

External alarm
Transmission wiring

Field settings

BS units (b) with ventilated enclosure safety measure

Code

Description

Value

[2-0]

Cluster indication

1: enable

[2-1]

Cluster number

1

[2-2]

Cluster configuration

0 (default): parallel

[2-4]

Safety measures

1 (default): enable

[2-7]

Ventilated enclosure

1 (default): enable

BS units (c) without safety measures

Code

Description

Value

[2-0]

Cluster indication

0 (default): disable

[2-4]

Safety measures

0: disable

BS units (d) with external alarm safety measure

Code

Description

Value

[2-0]

Cluster indication

0 (default): disable

[2-4]

Safety measures

1 (default): enable

[2-7]

Ventilated enclosure

0: disable

Note: 

 Some field settings need to be made on all main PCB's (A1P,

A2P  and  A3P)  of  the  same  BS  unit.  For  more  information,  see

"16.1 Making field settings"

 [

4

 34].

13

Unit installation

WARNING

The  installation  MUST  comply  with  the  requirements  that
apply  to  this  R32  equipment.  For  more  information,  see

"12 Special requirements for R32 units"

 [

4

 14].

13.1

Preparing the installation site

Avoid  installation  in  an  environment  with  a  lot  of  organic  solvents
such as ink and siloxane.

Do NOT install the unit in places often used as work place. In case
of  construction  works  (e.g.  grinding  works)  where  a  lot  of  dust  is
created, the unit MUST be covered.

Choose an installation location with sufficient space to carry the unit
in and out of the site.

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

13.1.1

Installation site requirements of the unit

CAUTION

Appliance NOT accessible to the general public, install it in
a secured area, protected from easy access.

This  unit  is  suitable  for  installation  in  a  commercial  and
light industrial environment.

CAUTION

This  equipment  is  NOT  intended  for  use  in  residential
locations  and  will  NOT  guarantee  to  provide  adequate
protection to radio reception in such locations.

NOTICE

The professional installer shall evaluate the EMC situation
before installation, if the equipment is installed closer than
30 m to a residential location.

NOTICE

The  installation  and  any  maintenance  requires  a
professional  with  relevant  EMC  experience  to  install  any
specific  EMC  mitigation  measures  defined  in  the  user
instructions.

NOTICE

The  equipment  described  in  this  manual  may  cause
electronic  noise  generated  from  radio-frequency  energy.
The  equipment  complies  to  specifications  that  are
designed  to  provide  reasonable  protection  against  such
interference.  However,  there  is  no  guarantee  that
interference will NOT occur in a particular installation.

It  is  therefore  recommended  to  install  the  equipment  and
electric  wires  in  such  a  way  that  they  keep  a  proper
distance from stereo equipment, personal computers, etc.

In  places  with  weak  reception,  keep  distances  of  3  m  or
more  to  avoid  electromagnetic  interference  of  other
equipment  and  use  conduit  tubes  for  power  and
transmission lines.

INFORMATION

Equipment  meets  the  requirement  for  commercial  and
light-industrial  location  when  professionally  installed  and
maintained.

INFORMATION

The sound pressure level is less than 70 dBA.

INFORMATION

Also read the following requirements:

▪ Service space requirements. See below in this topic.

▪ Refrigerant  piping  requirements.  See 

"14  Piping

installation"

 [

4

 28].

Safety measures differ depending on the total amount of refrigerant
in  the  system  and  on  the  floor  area.  See 

"12.3  To  determine  the

required safety measures"

 [

4

 14].

The  BS  unit  is  designed  for  indoor  installation  only.  Always  respect
the following conditions.

Ambient condition

Value

Indoor temperature

15~32°C DB

Содержание VRV 5 BS4A14AJV1B

Страница 1: ...Installation and operation manual VRV 5 branch selector unit English Installation and operation manual VRV 5 branch selector unit BS4A14AJV1B BS6A14AJV1B BS8A14AJV1B BS10A14AJV1B BS12A14AJV1B...

Страница 2: ...measure c External alarm d m kg Amin m All other floors a All other floors a Lowest under ground floor b No safety measure c No safety measure c External alarm d 5 16 15 16 35 207 104 207 6 23 18 23...

Страница 3: ...iai bus eksploatuojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo pred...

Страница 4: ...he products are used in accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the...

Страница 5: ...3 4 3 To install the drain piping 24 13 5 Installing the ventilation ducting 24 13 5 1 To install the ducting field supply 24 13 5 2 To install the duct closing plate 25 13 5 3 To switch the air in an...

Страница 6: ...approved by the manufacturer are used in the duct work WARNING Do NOT install operating ignition sources example open flames an operating gas appliance or an operating electric heater in the duct wor...

Страница 7: ...wer supply cables WARNING If the supply cord is damaged it MUST be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard WARNING Use an all pole disc...

Страница 8: ...enance purposes See 12 3 To determine the required safety measures 4 14 to check if your system meets the R32 safety requirements For the user 3 User safety instructions Always observe the following s...

Страница 9: ...ways have qualified service personnel confirm that the point of leakage has been repaired or corrected before resuming operation WARNING This unit contains electrical and hot parts WARNING Before oper...

Страница 10: ...structions from Daikin and in addition comply with applicable legislation and are performed by qualified persons only In Europe and areas where IEC standards apply EN IEC 60335 2 40 is the applicable...

Страница 11: ...the unit by yourself Ask a qualified service person to perform this work 6 1 Precautions for maintenance and service CAUTION See 3 User safety instructions 48 to acknowledge all related safety instruc...

Страница 12: ...ned malfunctions is evident investigate the system in accordance with the following procedures Malfunction Measure If a refrigerant leak occurs error code Actions will be taken by the system Do NOT tu...

Страница 13: ...it and options 11 1 About combining units and options 11 1 1 Possible options for the BS unit INFORMATION All possible options are mentioned in the option list below For more information about an opti...

Страница 14: ...he outdoor unit For installation of the indoor unit see the installation and operation manual delivered with the indoor unit For compatibility of indoor units see the latest version of the technical d...

Страница 15: ...arm e Ventilated enclosure Ventilated enclosure Use the total amount of refrigerant in the system and the area of the room in which the BS unit is installed to check what is the safety measure that ne...

Страница 16: ...ntrolled number of people are present accessible for persons not familiar with the necessary safety precautions To warn at a supervised location connect a supervisor remote controller to the system Th...

Страница 17: ...hen compared with the pressure of the surroundings The minimum required airflow rate AFROUT is 18 8 m h and the pressure drop generated by the BS unit should lead to a pressure inside the BS unit Pint...

Страница 18: ...parallel BS units are connected to a single extraction fan Each BS unit benefits from a direct airflow path to the extraction fan In case of a refrigerant leak in any BS unit the damper of that BS uni...

Страница 19: ...t run that simulates a refrigerant leak See 17 1 BS unit test run 438 for more details Field settings Multiple BS units in series one extraction fan Code Description Value 2 0 Cluster indication 1 ena...

Страница 20: ...ames an operating gas appliance or an operating electric heater 13 1 1 Installation site requirements of the unit CAUTION Appliance NOT accessible to the general public install it in a secured area pr...

Страница 21: ...length Keep drain piping as short as possible Drain pipe size Keep the pipe size equal to or greater than that of the connecting pipe vinyl pipe of 20 mm nominal diameter and 26 mm outer diameter Bad...

Страница 22: ...lt flow Ducting on both sides B Reversed flow Only ducting on the air outlet side B Reversed flow Ducting on both sides C No extraction ventilation installed 1 To extraction fan or another BS unit 2 F...

Страница 23: ...pension bolt Leave enough space for maneuvering with the unit between the nut and double nut 3 Position the unit by hooking the hanger brackets of the unit around the suspension bolts in between the t...

Страница 24: ...n hose Note Start on the screw part of the metal clamp work your way around the clamp and end overlapping your starting point 5 b a c d a Drain pipe connection attached to the unit b Drain hose access...

Страница 25: ...der the field supply insulation Create an overlap of 50 mm If the entire outlet duct is thermally insulated from the unit to the outside wall the accessory sealing material is not necessary a d e d e...

Страница 26: ...wire Store the screw in a safe place Cut the cable ties that fix the damper wire to the pipe and the one that bundles the damper wire a b b b a Damper wire b Cable ties 8 Remove the damper Remove the...

Страница 27: ...his makes the connection airtight Attach the damper with 4 screws 4 PH2 SW8 3 2 N m a b b b b c 1 2 a Damper wire b Screw c Damper 15 Connect the damper wires a b c 1 PH2 1 7 N m a Connector b Earth w...

Страница 28: ...a b c d BS4A a b b c d BS6 12A a Damper wire b Tie wrap to fix damper wire to piping field supply c Tie wrap to bundle the damper wire field supply d Leftmost wire fixing plate To re install the switc...

Страница 29: ...6 Maximum number of indoor units connected to BS units in refrigerant flow through c 64 14 2 Preparing refrigerant piping 14 2 1 Refrigerant piping requirements NOTICE The piping and other pressure co...

Страница 30: ...erant flow through with another BS unit and unused branch pipes when no indoor unit is connected to that branch pipe port 5 In case of stopper pipes install stopper pipe insulation tubes accessory Add...

Страница 31: ...art from each other Transmission wiring and power supply wiring may cross but may NOT run parallel In order to avoid any electrical interference the distance between both wirings should ALWAYS be at l...

Страница 32: ...e corresponding indoor unit multiple indoor units connected to the same branch the terminals F1 F2 Indoor unit X on the BS unit to the F1 F2 terminals on the first indoor unit Connect the F1 F2 termin...

Страница 33: ...tape e Transmission wiring F1 F2 f Insulation 15 4 To set the DIP switches The DIP switches are located on the PCB s A1P A2P BS6 12A and A3P BS10 12A A1P A2P A3P A B C D E F G H I J K L A B C D E F G...

Страница 34: ...MPLE a FAN output terminal b Relay c Extraction fan power supply d Extraction fan SVS output external alarm The SVS output is a potential free contact on terminal X6M that closes in case a leak is det...

Страница 35: ...Value Example Description Default situation Mode 1 Mode 2 Description Setting 8 in mode 2 Value 4 in mode 2 16 1 4 To access mode 1 or 2 Initialisation default situation NOTICE Be sure to turn ON the...

Страница 36: ...r more than 5 seconds Result Mode 2 is accessed 3 Push BS2 seven times Result Mode 2 setting 7 is addressed 4 Push BS3 1 time the value which is returned depending on the actual field situation is the...

Страница 37: ...on the 7 segment display of the outdoor unit This setting must only be made on the leftmost main PCB A1P of each BS unit 2 6 Commissioning check 0 default Incomplete 1 Completed 2 7 Setting to enable...

Страница 38: ...he BS unit test run The BS unit test run has to be performed on all BS units in the system before the test run of the outdoor unit The BS unit test run has to confirm that the required safety measures...

Страница 39: ...e airflow rate at the air inlet damper of the BS unit Tip Use the duct connection kit EKBSDCK and an anemometer with a funnel to conduct the entire airflow through the anemometer Postrequisite Remove...

Страница 40: ...uring BS unit test run Symptom The damper does not open Possible causes Corrective action Incorrect field settings Check if all field settings are made correctly When in parallel or series configurati...

Страница 41: ...by your local dealer This chapter gives you an overview of the most possible error codes and their descriptions as they appear on the user interface INFORMATION See the service manual for The complet...

Страница 42: ...PTC thermistor Q Insulated gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth leak circuit breaker Q L Overload protector Symbol Meaning Q M Thermo switch Q R Residual current device R R...

Страница 43: ...or for the product Authorised installer Technical skilled person who is qualified to install the product User Person who is owner of the product and or operates the product Applicable legislation All...

Страница 44: ...4P670163 1 2022 02 Copyright 2022 Daikin 4P670163 1 0000000L Verantwortung f r Energie und Umwelt...

Отзывы: