Si71-812
Troubleshooting
Troubleshooting
61
2.6
Damper System Error (Alarm)
Remote
Controller LCD
Display
Error Code
6A
Inspection
5
Unit No.
5
LED Indication
Remote Controller
5
Main Unit
5
Error Detection
Method
Measurement of damper motor limit switch ON/OFF time and temperatures detected by outdoor
and indoor air thermistor.
Error Generating
Conditions
When damper system error (alarm) and indoor (or outdoor) thermistor error are generated at
the same time.
When damper system error (alarm) occurs and values of indoor and outdoor air thermistor
meet frost conditions.
Possible Causes
Faulty damper motor or limit switch
Faulty indoor air thermistor
Faulty outdoor air thermistor
Frosting
Broken wire in cable
Faulty contact in connector (including relay connector)
Faulty control PC board (A1P) assembly
Troubleshooting
Check error record on
malfunction history
display in service
mode.
Is "
64
" recorded?
YES
YES
YES
Take corrective measures
specified for damper system
error (alarm).
(Remove the cause of problem,
and reset display.)
Take corrective measures
specified for damper system
error (alarm) and indoor and
outdoor air thermistor errors.
Take corrective measures
specified for damper system
error (alarm) and outdoor air
thermistor error.
Take corrective measures
specified for damper system
error (alarm) and indoor and
outdoor air thermistor error.
Are
"
6A
" and "
64
"
or "
65
" recorded?
NO
(HF006)
NO
Are
"
64
" and "
65
"
recorded?
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Содержание VKM100GAMV1
Страница 9: ...Introduction Si71 812 viii ...
Страница 10: ...Si71 812 General Constructions 1 Part 1 General Constructions 1 General Information 2 1 1 Features 2 ...
Страница 43: ...Operation Si71 812 34 Operation ...
Страница 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance ...
Страница 91: ...Troubleshooting Si71 812 82 Troubleshooting ...
Страница 92: ...Si71 812 Field Setting 83 Part 7 Field Setting 1 Field Setting 84 1 1 Field Setting and Test Run 84 ...
Страница 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 ...
Страница 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1 ...
Страница 103: ...Piping Diagram Si71 812 94 Appendix ...
Страница 105: ...Si71 812 ii Index ...