Si71-812
Troubleshooting
Troubleshooting
59
2.4
Outdoor Air Thermistor Error
Remote
Controller LCD
Display
Error Code
65
Inspection — Unit No.
5
LED Indication
Remote Controller
4
Main Unit
5
Error Detection
Method
Temperature detected by outside air temperature sensor is used to detect errors.
Error Generating
Conditions
When value detected by outside air temperature sensor is -40ºC or below (open circuit) or 70ºC
or higher (short-circuit).
Possible Causes
Faulty sensor
Broken wire
Faulty control PC board (A1P)
Faulty contact in connector
Troubleshooting
Note:
Note 1:
Refer to the thermistor temperature - resistance conversion table when measuring resistance.
Thermistor temperature - resistance conversion table
If measured value deviates significantly from above values, thermistor is faulty.
Use tester to check resistance
Remove outdoor air
thermistor (R2T) from
X13A (2P) on control
PC board (A1P), and
measure resistance.
Is
thermistor
normal?
Note 1
YES
NO
Replace outdoor
air thermistor.
If there is no faulty
contact, replace
control PC board.
(HF004)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Thermistor temperature Sensor resistance
Thermistor temperature Sensor resistance
-10ºC or less
108k
Ω
or more
22ºC
Approx. 23k
Ω
-5ºC
Approx. 85k
Ω
24ºC
Approx. 21k
Ω
0ºC
Approx. 66k
Ω
26ºC
Approx. 19k
Ω
5ºC
Approx. 51k
Ω
28ºC
Approx. 18k
Ω
10ºC
Approx. 40k
Ω
30ºC
Approx. 16k
Ω
14ºC
Approx. 33k
Ω
35ºC
Approx. 13k
Ω
16ºC
Approx. 30k
Ω
40ºC
Approx. 11k
Ω
18ºC
Approx. 27k
Ω
50ºC or more
7k
Ω
or less
20ºC
Approx. 25k
Ω
Continuity check
(HL028)
Содержание VKM100GAMV1
Страница 9: ...Introduction Si71 812 viii ...
Страница 10: ...Si71 812 General Constructions 1 Part 1 General Constructions 1 General Information 2 1 1 Features 2 ...
Страница 43: ...Operation Si71 812 34 Operation ...
Страница 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance ...
Страница 91: ...Troubleshooting Si71 812 82 Troubleshooting ...
Страница 92: ...Si71 812 Field Setting 83 Part 7 Field Setting 1 Field Setting 84 1 1 Field Setting and Test Run 84 ...
Страница 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 ...
Страница 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1 ...
Страница 103: ...Piping Diagram Si71 812 94 Appendix ...
Страница 105: ...Si71 812 ii Index ...