Troubleshooting
Service manual
26
VAM350~200 EKVDX32~100A2VEB
VRV system air conditioner
ESIE22-07 – 2022.02
3.2.7 A6-10-12-14-16 – Fan motor abnormality - overcurrent or IPM protection
VAM-J8 units
Trigger
Effect
Reset
PCB detects too high
current.
Units will stop operating.
Remote controller reset.
Sub code
Unit
Fan motor
Fan PCB
10
VAM350~650J8
Supply air
M1F
A2P
1000J8
Supply air
M2F
A3P
2000J8
Supply air (bottom)
M2F
A3P
12
VAM350~650J8
Exhaust air
M2F
A2P
1000J8
Exhaust air
M1F
A2P
2000J8
Exhaust air (bottom)
M1F
A2P
14
2000J8
Supply air (top)
M4F
A5P
16
2000J8
Exhaust air (top)
M3F
A4P
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check the power supply to the indoor unit. See Power supply.
Possible cause:
▪
Faulty or disturbance of the power supply (imbalance),
▪
Phase missing,
▪
Power drop,
▪
Short circuit.
2
Depending on your unit, perform a check of the appropriate indoor unit fan
motor (see table above). See Indoor unit fan motor.
Possible cause:
Faulty indoor unit fan motor.
3
Depending on your unit, perform a check of the appropriate indoor unit fan
PCB (see table above). See Indoor unit fan PCB.
Possible cause:
Faulty indoor unit fan PCB.
4
Perform a check of the indoor unit main PCB. See Indoor unit PCB.
Possible cause:
Faulty indoor unit main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
draft – 07/02/2022 15:12