250FC
Total Heat Exchanger
HRV (Heat Reclaim Ventilation)
4P415946-1 – 2015.08
Installation manual
14
■
Connecting the remote controller for HRV
The remote controller for HRV cannot be used for starting/stopping
operation or for timer operation. (The centralized control indication
will be lit.)
To set pre-cool/pre-heat function settings, change the remote control
air flow rate setting from medium (M) to high (H), etc., perform initial
settings from the remote controller for HRV.
Since it will become a two-remote-control system, perform master/
slave setting as shown below.
Refer to "preforming initial settings" in the remote control instruction
manual.
Example 4:
To set the pre-cool/pre-heat reservation function to on and have the
HRV start operating 60 minutes after the air conditioner has started,
set the same numbers as shown in example 1 using the remote
controller for HRV.
Example 5:
To increase the remote control air ventilation rate setting from
Medium to High, set the same numbers as shown in example 2 using
the remote controller for HRV.
Set the switches of the HRV unit PCB to the default factory settings.
■
Determination of heating/cooling selection rights for VRV-
systems is performed using the remote controller for HRV.
The heating/cooling selection rights can be enabled or disabled
using the ventilation mode button of the remote controller for
HRV.
This operation cannot be performed with the remote controller
for air conditioner.
Direct duct connection system for 1-group operation system
Line connections and the settings of the switches on the HRV unit
PCB should be the same as for "Standard system for 1-group
system".
Set the switches of the HRV unit PCB to the default factory settings.
1
Be sure to set the initial settings to Direct duct connection:
Enabled.
■
When the remote controller for HRV is not yet connected,
initial settings can be performed using the air conditioner
remote control. Set the mode number to "17", the setting
switch number to "5", and the setting position number to "02"
according to the procedure in
■
When the remote controller for HRV, initial settings should be
performed using the remote controller for HRV. Set the same
numbers as described above when using the remote
controller for air conditioner according to the procedure
"Making initial settings" in the remote control instruction
manual.
2
Settings for other HRV functions should be made using the
same method as in "Standard system for 1-group system".
Linked control with more than two groups
■
Mount the optional
KRP2A61 Adapter PCB for
remote control on the
electric component
mounting base of one HRV
unit.
■
A maximum of 64 air
conditioners and HRV
units can be connected to
the F1 and F2 terminals.
■
Use the remote controller
of the air conditioner to
make the initial settings.
Remote control
Master/slave setting
Remote controller for air conditioner
Slave
Remote controller for HRV
Master
Air ventilation
rate setting
using remote
control
Default factory settings
When set
as in example 5
Low
Low (L) air flow rate
Low (L) air flow rate
High
Medium (M) air flow rate
High (H) air flow rate
Default factory settings
air flow rate
Heating/cooling selection rights
Operation switchover control display
Enabled
Not lit
Disabled
Lit
Not set
Blinking
P1
P2
P1P2
P1 P2
P1 P2
VRV
1
2
5
3
4
1
Remote controller for air
conditioner
4
Medium (M) air flow rate
2
Remote controller for HRV
5
When the remote controller for
HRV is connected, set the
switches on the HRV unit PCB to
the default factory settings.
3
Maximum connection line length:
500 m
H M L
SS1
1
Remote controller for air
conditioner
2
Connecting line can be
extended up to 1000 m
maximum
3
Optional distant control
adapter KRP2A61
P1
P2
P1P2
P1 P2
P1 P2
VRV
1
2
3
4
1
Remote controller for air
conditioner
3
Maximum connection line length:
500 m
2
Remote controller for HRV
4
Medium (M) air flow rate
VRV
VRV
HRV 1
HRV 2
X11A
F1 F2
P1
P2
P1 P2
F1 F2
F1 F2
1
2
3
Содержание VAM250FC
Страница 22: ...NOTES...
Страница 23: ...NOTES...
Страница 24: ...4P415946 1 2015 08 Copyright 2015 Daikin...