Installation manual
13
250FC
Total Heat Exchanger
HRV (Heat Reclaim Ventilation)
4P415946-1 – 2015.08
12.
Push the button "
" and set the time.
Each time when "
" is pushed, the time advances one hour.
Each time when "
" is pushed, the time goes back one hour.
13.
Push the button "
".
Then, the reservation is finished.
Either "
" or "
" changes from flashing to lighting.
After the reservation is finished, the remaining time is indicated
in the display.
For cancelling the timer operation, push the button "
" once
again.
The indication disappears.
14.
If you press these buttons when using independent operation of
the HRV unit, the message "NOT AVAILABLE" will appear on the
display for a few seconds.
Independent system
When connecting to Remote controller for HRV
For raising the remote-controlled ventilation air flow rate from "High"
to "Ultra-High", connect the remote controller for the air-conditioner to
HRV and make settings on site.
(Refer to "Initial setting" under item
Set the switches on the printed circuit board to the factory setting.
Wiring and connections in combination with
"VRV-SYSTEM"
Standard 1-group linked-control system
■
The remote control of the air conditioner can be used to control
up to 16 air conditioner indoor units and HRV units.
■
Initial settings can be made for the functions of the HRV units
(pre-cool/pre-heat, ventilation air flow, ventilation mode and
"Fresh-Up").
Use the remote controller of the air conditioner to make the initial
settings for the HRV units.
Refer to "Initial setting" under Item
Pre-cool/pre-heat function
When the pre-cool/pre-heat function is set, the HRV unit switches on
at the preset time (30, 45 or 60 minutes) after the VRV-system air
conditioner begins cooling or heating operation. The function is set
OFF at the factory. Therefore, to use this function, the initial setting
must be made using the remote controller of the air conditioner.
If the air conditioner is re-started within two hours after the operation
was stopped, this function does not operate.
Example 1:
To switch on the pre-cool/pre-heat function, and turn on the HRV unit
60 minutes after the air conditioner is turned on.
•
Set the mode No. to "17" for group control, or "27" for individual
control, the setting switch No. to "2" and the setting position No.
to "02"
•
Set the mode No. to "17" for group control, or "27" for individual
control, the setting switch No. to "3" and the setting position No.
to "03"
Example 2:
To switch the ventilation air flow to ultra high setting. (The units are
set at the high air flow setting at the factory)
•
Set the mode No. to "17" for group control, or "27" for individual
control, the setting switch No. to "4" and the setting position No.
to "02"
Example 3:
To switch the ventilation air flow to low setting.
•
Set the mode No. to "19" for group control, or "29" for individual
control, the setting switch No. to "0" and the setting position No.
to "01"
Factory setting
air flow rate
Factory setting
air flow rate
P1 P2
P1 P2
P1 P2
P1 P2
HRV
HRV
1
2
5
3
4
6
1
Master unit
4
Switch position: Master
2
Slave unit
5
Remote controller for HRV
3
Switch position: Slave
6
Maximum connection line length:
500 m
H M L
SS1
H M L
SS1
P1
P2
P1 P2
P1 P2
P1 P2
VRV
HRV
1
2
3
1
Remote controller for air
conditioner
3
Connecting line can be extended
up to 500 m maximum
2
Remote controller for HRV
Содержание VAM250FC
Страница 22: ...NOTES...
Страница 23: ...NOTES...
Страница 24: ...4P415946 1 2015 08 Copyright 2015 Daikin...