background image

13 Configuration

Installation and operation manual

18

VAM350~2000J8VEB

Heat reclaim ventilation unit

4P664011-1 – 2021.08

NOR. H M

NOR.

H M

SS1

SS1

q

a

b

e

c

d

f

g

h

i

j

k

l

m

n

o
p

X20A

X21A

X41A

X42A

X38A

X14A

X33A

X35A

X70A

X24A

X26A

X28A

X22A

X29A

X5A X6A X12A X11A

J3 J2 J1 JC

F2 F1 N/P2 P/P1

J3 J2 J1 JC

F2 F1 P2 P1

X27A

F1U 6.3A

L

N

a

Power supply

b

Terminals

c

Bypass damper

d

Bypass damper (only models 1500+2000 bottom unit)

e

External damper (field supply)

f

Fan communications

g

KRP2A51 (option)

h

Controller

i

Central control

j

External input

k

Outdoor air thermistor

l

Indoor air thermistor

m

Bypass damper (only models 1500+2000 bottom unit)

n

Bypass damper

o

BRP4A50A (optional accessory)

p

CO₂ sensor

q

Factory setting (No operation if setting is changed)

WARNING

If  a  gap  is  present  at  the  cable  entry,  wrap  the  cable  (or
cables) with the sealing material from the accessory bag.

This  will  prevent  small  objects  (such  as  children's
fingers,  ...  etc.)  as  well  as  fluid  droplets  from  entering  the
unit.

+

+

=

=

NOTICE

Factory settings: Do NOT change the switch settings when
a controller is connected. SS1 is a setting switch to operate
the  unit  without  controller.  Changing  the  switch  setting
when  a  controller  is  connected  will  stop  the  unit  from
operating  normally.  Keep  the  switch  on  the  PCB  in  the
factory setting position.

13

Configuration

13.1

To change settings

The  heat  reclaim  ventilation  unit  settings  can  be  adjusted  using  the
controller  of  either  the  heat  reclaim  ventilation  unit  or  the  air
conditioner.

The settings (format: e.g. 19(29)-1-02), that are used in this chapter
are composed of 3 parts, divided by "-":

▪ Mode  number:  e.g.  19(29),  where  19  is  the  mode  number  for

group settings and 29 is the mode number for individual settings.

▪ Switch number: e.g. 1

▪ Position number: e.g. 02

Initial settings

▪ Mode  numbers  17,  18,  and  19:  group  control  of  heat  reclaim

ventilation units.

NOTICE

Field  setting  mode  numbers  17,  18  and  19  CANNOT  be
used with EKVDX indoor units.

▪ Mode  numbers  27,  28,  and  29:  individual  control  or  when

operating with the optional EKVDX units.

Case 1: Change settings with BRC1E53

Make sure that the switch box lid on the heat reclaim ventilation unit
is closed.

1

Briefly press a button to turn on the screen light.

2

Press  and  hold  the  Cancel  button  (a)  for  at  least  4  seconds  to
enter the Service Settings menu.

3

Go  to  Field  Settings  with  the  Up/Down  buttons  and  press  the
Menu/Enter button (b).

4

Press  the  Left/Right  buttons  to  highlight  the  number  under
Mode.

5

Press  the  Up/Down  buttons  to  select  the  required  mode
number.

Result: 

From  mode  20  and  up,  you  also  have  to  select  a  unit

number for individual control.

6

Use  the  Left/Right  buttons  to  highlight  the  number  under  Unit
No..

7

Use  the  Up/Down  buttons  to  select  an  indoor  unit  number.
Selecting a unit number is NOT necessary when configuring the
entire group.

8

Use the Left/Right buttons to select a switch number (0 to 15) to
change.

In case of individual settings:

Field Settings

Unit No.

0

Mode

20

Setting

Return

In case of group settings:

Field Settings

Mode

10

Setting

Return

9

Use  the  Up/Down  buttons  to  select  the  required  position
number.

10

Press the Menu/Enter (b) button and confirm the selection with
Yes.

Содержание VAM-J8 Series

Страница 1: ...n and operation manual Heat reclaim ventilation unit English Installation and operation manual Heat reclaim ventilation unit VAM350J8VEB VAM500J8VEB VAM650J8VEB VAM800J8VEB VAM1000J8VEB VAM1500J8VEB V...

Страница 2: ...orabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartu...

Страница 3: ...troller 25 14 Commissioning 25 14 1 Checklist before commissioning 25 14 2 Checklist during commissioning 26 14 2 1 About the test run 26 15 Troubleshooting 26 15 1 Solving problems based on error cod...

Страница 4: ...the applicable legislation Make electrical connections to the fixed wiring All components procured on site and all electrical construction MUST comply with the applicable legislation WARNING After fin...

Страница 5: ...nd may cause accidents WARNING ALWAYS use multicore cable for power supply cables WARNING Use an all pole disconnection type breaker with at least 3 mm between the contact point gaps that provide full...

Страница 6: ...VDX In order to be effective the installed unit MUST be electrically powered at all times except for short service periods CAUTION Before accessing make sure to turn OFF the operation switch and disco...

Страница 7: ...OTICE NEVER wash the heat exchange element with water NEVER touch the heat exchange element paper because it can be damaged if it is forced Do NOT crush the heat exchange element To clean the heat exc...

Страница 8: ...e at all Check if there is no power failure Wait until power is restored and restart operation Check if no fuse has blown or breaker is activated Change the fuse or reset the breaker if necessary Chec...

Страница 9: ...VAM unit location Temperature 0 C DB 40 C DB Relative humidity 80 It is possible that due to condensation the paper heat exchanger deteriorates when the unit operates in conditions with high indoor hu...

Страница 10: ...ion is effective to reduce blowing noises When selecting installation materials consider the required volume of air flow and the acceptable level of noise for that particular installation When room ai...

Страница 11: ...pter PCB KRP2A51 in the installation box KRP1BA101 4 Follow the installation instructions provided with the option kits BRP4A50A KRP2A51 and KRP1BA101 5 Guide the PCB wire through the dedicated holes...

Страница 12: ...xample if 2 units are installed closely together only 1 inspection hole is required for maintaining or replacing filters heat exchange elements a b c a Control box b Service cover c Inspection hole Ke...

Страница 13: ...optional EKVDX see EKVDX operation and installation manual Models 350 1000 b c a d a Name Plate Models 1500 2000 d c e e f a Aluminium tape field supply b Insulation material field supply c Duct flan...

Страница 14: ...rminal Loose connections may reduce the protection For the controller wiring refer to the installation manual of the controller delivered with the controller Wiring example VRV HRV P1 P1 P1 P2 P2 P2 L...

Страница 15: ...ptional controller i Power supply cable j Wires for connection of additional external damper supplied accessory k Insulated splices closed barrel connector 0 75 mm field supply l Double or reinforced...

Страница 16: ...l controller Ii Power supply cable j Wires for connection of additional external damper supplied accessory k Insulated splices closed barrel connector 0 75 mm field supply l Double or reinforced insul...

Страница 17: ...e VAM is switched off The VAM main PCB provides a contact for an external damper PCB X24A a b c d a VAM b External damper c External damper earthing d Power source CAUTION Follow the instructions belo...

Страница 18: ...or the air conditioner The settings format e g 19 29 1 02 that are used in this chapter are composed of 3 parts divided by Mode number e g 19 29 where 19 is the mode number for group settings and 29 i...

Страница 19: ...n b to select a mode number Result The code display is blinking 3 To configure settings for individual units under group control press the Timer setting on off button c and select the number of the un...

Страница 20: ...29 C 30 C 8 Central zone link No Yes 9 Preheat time extension c 0 minutes 30 minutes 60 minutes 90 minutes 18 28 0 External signal g JC J2 Last command Priority on external input Priority on operation...

Страница 21: ...y system n OFF ON 1A 0 Fresh up operation k OFF ON a Factory settings are marked with a grey background b In case VAM and EKVDX are combined and the R32 safety system of the VAM is active the nighttim...

Страница 22: ...must be equal in order to have a balanced system Models 350 1000 Settings 19 29 2 and 19 29 3 Balance exhaust air and supply air with fan steps 1 15 based on the air flow curves see the databook and t...

Страница 23: ...ting 19 29 0 04 CANNOT be configured if the outside temperature is 10 C which is out of the operation range Setting 19 29 0 05 CANNOT be configured if the outside temperature is 5 C In this case error...

Страница 24: ...tdoor air is supplied to the room without heat exchange with the room air Time to clean filter indication When the filter pressure drop becomes too large the following message or icon is displayed at...

Страница 25: ...on of the heat reclaim ventilation units is linked to the air conditioners this indication may be displayed While this indication is displayed the heat reclaim ventilation units CANNOT be turned on or...

Страница 26: ...ion of the system turn on the power of the heat reclaim ventilation units Refer to the manual of the controller of each unit controller for air conditioner central controller etc to conduct a trial op...

Страница 27: ...power supply printed circuit board Symbols Field wiring Terminals Connectors Protective earth Noiseless earth Colours BLK Black BLU Blue BRN Brown GRN Green ORG Orange RED Red WHT White YLW Yellow Tr...

Страница 28: ...and operation manual 28 VAM350 2000J8VEB Heat reclaim ventilation unit 4P664011 1 2021 08 17 2 Service space 50 a 150 250 mm A B a Service space Models A B VAM350 500 900 mm 675 mm VAM650 1100 mm 700...

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ...4P664011 1 2021 08 Copyright 2021 Daikin 4P664011 1 0000000G Verantwortung f r Energie und Umwelt...

Отзывы: