
SiE71-202
Supplementary Explanation
Supplementary Explanation
57
Unit No.
reallocation (Mode
No.45)
Step 1
With equipment in field setting mode, press the
button for more than 4 seconds to enter
service mode.
Step 2
Mode No.: UP
↔
Mode No.: DOWN
Use [MODE] and [AIR VOLUME] to select mode No.45.
Step 3
Use
to select setting Unit No.
Step 4
Press
or
button to select Unit No. after reallocation.
Step 5
Press
button once to enter settings.
Step 6
Press
button to return to normal mode.
Unit No. before reallocation
Unit No. after reallocation
3
4
1, 6
5
4
2
(HL042)
Field setting mode
Mode No.
Содержание VAM 150FAVE
Страница 5: ...SiE71 202 iv Table of Contents ...
Страница 10: ...SiE71 202 General Constructions 1 Part 1 General Constructions 1 General Constructions 2 1 1 Explanation 2 ...
Страница 13: ...General Constructions SiE71 202 4 General Constructions ...
Страница 14: ...SiE71 202 Product Specification 5 Part 2 Product Specification 1 Product Specification 6 1 1 Specification 6 ...
Страница 37: ...Control Functions SiE71 202 28 Control Functions ...
Страница 41: ...Circuit Operations SiE71 202 32 Circuit Operations ...
Страница 73: ...Supplementary Explanation SiE71 202 64 Supplementary Explanation ...
Страница 74: ...SiE71 202 Appendix 65 Part 9 Appendix 1 Appendix 66 1 1 Wiring Diagram 66 ...
Страница 77: ...Appendix SiE71 202 68 Appendix ...
Страница 81: ...SiE71 202 iv Index ...