SiE71-202
Troubleshooting
Troubleshooting
43
1.10
Data Transmission Error (LCD Remote Controller)
Remote Controller
LCD Display
Error Code
U5
Inspection
5
Unit No.
1
LED Indication
Remote Controller
5
Main Unit
5
Error Detection
Method
Microcomputer checks if data is transmitted properly between main unit and remote controller.
Error Generating
Conditions
When data transmission is not performed correctly for a certain time period.
Possible Causes
Erroneous connection
Faulty remote controller setting
Faulty remote controller
Troubleshooting
Is
master-slave
selection switch
properly set?
YES
YES
Correct wiring.
Replace remote controller.
Set one master-slave selection
switch to Master, and set the
other to Slave. Then turn off
power, and restart operation.
Replace either master or slave
remote controller.
Is
remote
controller
other than
dedicated LCD
remote controller
connected to
remote
controller
cable?
NO
(HF009)
NO
Is
master-slave
remote control
used?
NO
YES
Содержание VAM 1000FAVE
Страница 5: ...SiE71 202 iv Table of Contents ...
Страница 10: ...SiE71 202 General Constructions 1 Part 1 General Constructions 1 General Constructions 2 1 1 Explanation 2 ...
Страница 13: ...General Constructions SiE71 202 4 General Constructions ...
Страница 14: ...SiE71 202 Product Specification 5 Part 2 Product Specification 1 Product Specification 6 1 1 Specification 6 ...
Страница 37: ...Control Functions SiE71 202 28 Control Functions ...
Страница 41: ...Circuit Operations SiE71 202 32 Circuit Operations ...
Страница 73: ...Supplementary Explanation SiE71 202 64 Supplementary Explanation ...
Страница 74: ...SiE71 202 Appendix 65 Part 9 Appendix 1 Appendix 66 1 1 Wiring Diagram 66 ...
Страница 77: ...Appendix SiE71 202 68 Appendix ...
Страница 81: ...SiE71 202 iv Index ...