SiE71-202
Troubleshooting
Troubleshooting
35
1.2
Overall Alarm
Remote Controller
LCD Display
Error Code
60
Inspection
—
Unit No.
5
LED Indication
Remote Controller
4
Main Unit
5
Error Detection
Method
Abnormalities are detected based on open circuit in external input terminals (J1-JC).
Error Generating
Conditions
When external input terminal (J1-JC) short-circuit during operation
(“Overall Alarm” must be set in field setting mode).
Possible Causes
Faulty external device
Broken wire
Faulty control PCB
Troubleshooting
Measure resistance
between external
input terminals
(J1-JC).
Is
resistance
200
Ω
or
lower?
YES
YES
Remove the cause of error in
connected external device.
Check wires for abnormalities
(broken wire, faulty contact,
etc.).
Replace control PCB.
Is
connected
external device
operating
properly?
NO
(HF001)
NO
Содержание VAM 1000FAVE
Страница 5: ...SiE71 202 iv Table of Contents ...
Страница 10: ...SiE71 202 General Constructions 1 Part 1 General Constructions 1 General Constructions 2 1 1 Explanation 2 ...
Страница 13: ...General Constructions SiE71 202 4 General Constructions ...
Страница 14: ...SiE71 202 Product Specification 5 Part 2 Product Specification 1 Product Specification 6 1 1 Specification 6 ...
Страница 37: ...Control Functions SiE71 202 28 Control Functions ...
Страница 41: ...Circuit Operations SiE71 202 32 Circuit Operations ...
Страница 73: ...Supplementary Explanation SiE71 202 64 Supplementary Explanation ...
Страница 74: ...SiE71 202 Appendix 65 Part 9 Appendix 1 Appendix 66 1 1 Wiring Diagram 66 ...
Страница 77: ...Appendix SiE71 202 68 Appendix ...
Страница 81: ...SiE71 202 iv Index ...