Product Specification
SiE71-202
6
Product Specification
1. Product Specification
1.1
Specification
Test conditions are as follows
Notes:
1. Operation sound is measured at 1.5 m below the center the body.
2. Fan speed can be changed over to Low mode or High mode.
3. Operating sound is measured in an anechoic chamber.
Operating sound level generally become greater than this value depending on the operating conditions,
reflected sound, and peripheral noise.
4. The sound level at the air discharge port is about 8 dB higher than the unit’s operating sound.
(50 / 60Hz)
Model Name
VAM150FAVE
VAM250FAVE
VAM350FAVE
Power Supply
Single Phase 220 – 240 V / 220 V, 50 / 60 Hz
Temperature Exchanging
Efficiency
Ultra-High
%
74 / 74
72 / 72
75 / 75
High
%
74 / 74
72 / 72
75 / 75
Low
%
79 / 80
77 / 77
80 / 81
Enthalpy
Exchange
Efficiency
Cooling
Ultra-High
%
58 / 58
58 / 58
61 / 61
High
%
58 / 58
58 / 58
61 / 61
Low
%
64 / 66
62 / 63
67 / 68
Heating
Ultra-High
%
64 / 64
64 / 64
65 / 65
High
%
64 / 64
64 / 64
65 / 65
Low
%
69 / 71
68 / 69
70 / 71
Casing
Galvanized Steel Plate
Insulating Material
Self-extinguishable Urethane Foam
Dimensions
H
×
W
×
D
mm
269
×
760
×
509
269
×
760
×
509
285
×
812
×
800
Heat Exchanging System
Air to Air Cross Flow Total Heat (Sensible Heat + Latent Heat) Exchange
Heat Exchanging Element
Specially Processed Nonflammable Paper
Air Filter
Multidirectional Fibrous Fleeces
Fan
Type
Sirocco Fan
Fan
Speed
Ultra-High
m
³
/ h
150 / 150
250 / 250
350 / 350
High
m
³
/ h
150 / 150
250 / 250
350 / 350
Low
m
³
/ h
110 / 110
155 / 145
230 / 210
External
Static
Pressure
Ultra-High
Pa
69 / 98
64 / 98
98 / 142
High
Pa
39 / 54
39 / 54
70 / 85
Low
Pa
20 / 24
20 / 20
25 / 15
Fan Motor
Type
Open Type Capacitor Permanent Split-phase Induction Motor, 4 Poles
×
2
Motor Output
kW
0.030
×
2
0.030
×
2
0.090
×
2
Operating
Sound
Heat
Exchange
Mode
Ultra-High
dBA
27 – 28.5 / 28.52
28 – 29 / 29.5
32 – 34 / 34.5
High
dBA
26 – 27.5 / 26.5
26 – 27 / 26
31.5 – 33 / 32
Low
dBA
20.5 – 21.5 / 19
21 – 22 / 19.5
23.5 – 26 / 22
Bypass
Mode
Ultra-High
dBA
27 – 28.5 / 28
28 – 29 / 29
32 – 34 / 34.5
High
dBA
26.5 – 27.5 / 27
27 – 28 / 27
31 – 32.5 / 33
Low
dBA
20.5 – 21.5 / 20
21 – 22 / 20.5
24.5 – 26.5 / 22
Operation Range (Ambient)
–15˚C to 50˚CDB (80% RH or Less)
Connection Duct Diameter
mm
φ
100
φ
150
φ
150
Weight
kg
24
24
33
Drawing Number
4D020371A
4D020372A
4D020373A
Condition
Indoor
Outdoor
˚CDB
R·H (%)
˚CDB
R·H (%)
Cooling condition
27
50
35
60
Heating condition
20
40
7
70
Содержание VAM 1000FAVE
Страница 5: ...SiE71 202 iv Table of Contents ...
Страница 10: ...SiE71 202 General Constructions 1 Part 1 General Constructions 1 General Constructions 2 1 1 Explanation 2 ...
Страница 13: ...General Constructions SiE71 202 4 General Constructions ...
Страница 14: ...SiE71 202 Product Specification 5 Part 2 Product Specification 1 Product Specification 6 1 1 Specification 6 ...
Страница 37: ...Control Functions SiE71 202 28 Control Functions ...
Страница 41: ...Circuit Operations SiE71 202 32 Circuit Operations ...
Страница 73: ...Supplementary Explanation SiE71 202 64 Supplementary Explanation ...
Страница 74: ...SiE71 202 Appendix 65 Part 9 Appendix 1 Appendix 66 1 1 Wiring Diagram 66 ...
Страница 77: ...Appendix SiE71 202 68 Appendix ...
Страница 81: ...SiE71 202 iv Index ...