Si-93
Supplementary Explanation
Supplementary Explanation
53
1. Supplementary Explanation
1.1
Field Setting, Service Mode Operation
1.1.1
Field Setting
Initial setting (mode
Nos. 17, 27, 18, 28)
4
3
6
1, 7
5
2
Unit No.
Mode No.
Setting position No.
Field setting mode
Setting switch No.
(HL039)
Step 1
With equipment in normal mode, press the
button for more than 4 seconds to enter field
setting mode.
Step 2
Mode No.: UP
↔
Mode No.: DOWN
Use [MODE] and [AIR VOLUME] to select desired mode No.
Step 3
To setting heat reclaim ventilation units by group, press
button and select desired unit
No.
Step 4
Press
button to select desired setting switch No.
Step 5
Press
button to select desired setting position No.
Step 6
Press
button to enter settings.
Step 7
Press
button to return to normal mode.
Содержание VAM 1000EJ
Страница 5: ...Si 93 iv Table of Contents ...
Страница 7: ...Introduction Si 93 vi 1 1 1 Cautions in Repair Warning ...
Страница 8: ...Si 93 Introduction vii ...
Страница 10: ...Si 93 General Constructions 1 Part 1 General Constructions 1 General Constructions 3 1 1 Explanation 3 ...
Страница 11: ...Si 93 2 General Constructions ...
Страница 15: ...Si 93 6 Operation ...
Страница 21: ...Si 93 12 Maintenance ...
Страница 27: ...Si 93 18 Control Functions ...
Страница 35: ...Si 93 26 Circuit Operations ...
Страница 39: ...Si 93 30 Troubleshooting ...
Страница 59: ...Troubleshooting Si 93 50 Troubleshooting ...
Страница 61: ...Si 93 52 Supplementary Explanation ...
Страница 72: ...Si 93 Appendix 63 Part 8 Appendix 1 Appendix 65 1 1 Wiring Diagram 65 ...
Страница 73: ...Si 93 64 Appendix ...
Страница 74: ...Si 93 Appendix Appendix 65 1 Appendix 1 1 Wiring Diagram VAM500EJVE VAM800EJVE VAM1000EJVE ...
Страница 75: ...Appendix Si 93 66 Appendix VAM2000EJVE ...
Страница 79: ...Si 93 iv Index ...
Страница 81: ...Si 93 vi Drawings Flow Charts When no indication is displayed on remote controller 45 Wiring Diagram 65 ...