Circuit Functions
www.DaikinApplied.com 95
IOM 1207-6 • TRAILBLAZER
®
MODEL AGZ CHILLERS
Cycle Timers
A minimum time between starts of the compressor and a
minimum time between shutdown and start of the compressor
shall be enforced. The time values are determined by the
Start-start Timer and Stop-start Timer setpoints.
These cycle timers should not be enforced through cycling of
power to the chiller. This means that if power is cycled, the
cycle timers should not be active.
These timers may be cleared via a setting on the controller.
Condenser Fan Control
Condenser fan control should stage fans as needed any time
compressors are running on the circuit. All fans and solenoid
valves will be off when the circuit is in the off and preopen
states. Condenser fan digital outputs will be turned on or
off immediately for condenser stage changes. Condenser
solenoid valve outputs will turn on immediately when a stage
up requires the output to turn on, but will have a delay for
turning off during a stage down. This delay is 20 seconds. If
the circuit shuts off then the condenser solenoid valve outputs
will turn off without a delay.
Condenser Staging
Condenser staging will use up to 5 digital outputs for control of
condenser fans and a digital output for control of a condenser
solenoid valve. When equipped with condenser fan VFDs, the
speed signal(s) also starts and stops the fan that is connected
to the VFD. The total number of fans on shall be adjusted
with changes of one fan at a time. The tables below show the
outputs energized for each stage.
Figure 72: 2 Fans per Circuit - Unit Numbering Schematic
Table 57: 2 Fans per Circuit - Without Fan VFD
Circuit 1
Description
Output
Fans
Stage
1
2
3
4
5
6
Fan Output 1
UC DO3
Fan 11 On On --
--
--
--
Fan Output 2
UC DO4
Fan 12
On --
--
--
--
Circuit 2
Description
Output
Fans
Stage
1
2
3
4
5
6
Fan Output 1
UC DO7
Fan 21 On On --
--
--
--
Fan Output 2
UC DO8
Fan 22
On --
--
--
--
Table 58: 2 Fans per Circuit - With 1 Fan VFD per Circuit
Circuit 1
Description
Output
Fans
Stage
1
2
3
4
5
6
Speed Signal 1 UC X5
Fan 11 On On --
--
--
--
Fan Output 2
UC DO4
Fan 12
On --
--
--
--
Circuit 2
Description
Output
Fans
Stage
1
2
3
4
5
6
Speed Signal 1 UC X6
Fan 21 On On --
--
--
--
Fan Output 2
UC DO8
Fan 22
On --
--
--
--
Figure 73: 3 Fans per Circuit - Unit Numbering Schematic
Table 59: 3 Fans per Circuit - Without Fan VFD
Circuit 1
Description
Output
Fans
Stage
1
2
3
4
5
6
Fan Output 1
UC DO3
Fan 11
On On On --
--
--
Fan Output 2
UC DO4
Fan 12
On On --
--
--
Fan Output 3
UC DO5
Fan 13
On
Condenser SV UC X7
SV 11
On
Circuit 2
Description
Output
Fans
Stage
1
2
3
4
5
6
Fan Output 1
UC DO7
Fan 21
On On On --
--
--
Fan Output 2
UC DO8
Fan 22
On On --
--
--
Fan Output 3
UC DO9
Fan 23
On --
--
--
Condenser SV UC X8
SV 21
On --
--
--
Control Panel
Fan 11
Fan 21
Fan 22
Fan 12
2-Fan Unit Locations and Numbering
Control Panel
Fan 11
Fan 12
Fan 21
Fan 23
Fan 13
Fan 22
3-Fan Unit Locations and Numbering