Troubleshooting
SiBE05-722EE
72
Service Diagnosis
4.7
Low-voltage Detection or Over-voltage Detection
Error Code
U2
Method of Error
Detection
Low-voltage detection:
An abnormal voltage drop is detected by the DC voltage detection circuit.
Over-voltage detection:
An abnormal voltage rise is detected by the over-voltage detection circuit.
Error Decision
Conditions
Low-voltage detection:
The voltage detected by the DC voltage detection circuit is below 180 V.
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Over-voltage detection:
An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer.
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Supposed
Causes
Power supply voltage is not as specified.
Defective DC voltage detection circuit
Defective over-voltage detection circuit
Defective PAM control part
Disconnection of compressor harness
Short circuit inside the fan motor winding
Noise
Momentary drop of voltage
Momentary power failure
Defective outdoor unit PCB
Содержание Super Multi NX FLKS25BAVMB
Страница 11: ...SiBE05 722EE List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 17: ...SiBE05 722EE Specifications 7 Part 2 Specifications 1 Specifications 8 1 1 Cooling Only 8 1 2 Heat Pump 11...
Страница 65: ...SiBE05 722EE Remote Controller 55 Part 5 Remote Controller 1 Remote Controller 56...