Troubleshooting for Outdoor Unit
Service Diagnosis
355
7.15 Output Overcurrent Detection
Remote
Controller
Display
L5
Outdoor Unit LED
Display
A
j
1
h
2
h
3
i
4
h
5
h
Method of
Malfunction
Detection
An output overcurrent is detected by checking the current that flows in the inverter DC section.
Malfunction
Decision
Conditions
A position signal error occurs while the compressor is running.
A speed error occurs while the compressor is running.
An output overcurrent signal is fed from the output overcurrent detection circuit to the
microcomputer.
If the error repeats 16 times, the system is shut down.
Reset condition: Continuous run for about 5 minutes without any other error
Supposed
Causes
Defective power transistor
Wrong internal wiring
Abnormal supply voltage
Defective outdoor unit PCB
Closed stop valve
Defective compressor
Poor installation condition