2
|
Components
Service manual
68
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01C – 2020.07
a a
b
c
d
e
a
Grouding wire screw
b
Heat exchanger thermistor
c
Indoor unit PCB
d
Switch box screw
e
Switch box
5
Route the connectors of the indoor unit fan motor, swing flap motor and
swing raster motor (if equipped) inside the switch box and connect them to
the indoor unit PCB.
6
Install and tighten the screw to secure the switch box.
7
Install the heat exchanger thermistor in its holder.
8
Connect the grounding wires to the heat exchanger using the screws.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
2.6 Indoor unit main PCB
2.6.1 Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a power check of the indoor unit main PCB
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Turn ON the power of the unit.
2
Measure the voltage between the black and white wires on the PCB. The
measured voltage MUST be 16 V DC.