1
|
Troubleshooting
Service manual
18
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01C – 2020.07
1.5.15 F8-00 – System shutdown due to compressor internal temperature abnormality
Trigger
Effect
Reset
Temperature discharge
pipe thermistor exceeds
the determined limit.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the refrigerant circuit. See
123].
Possible cause:
▪
Stop valve is closed,
▪
Clogged refrigerant circuit,
▪
Refrigerant circuit NOT charged correctly,
▪
Humidity in the refrigerant circuit,
▪
Non-condensables in the refrigerant circuit,
▪
Leaking refrigerant circuit.
2
Perform
a
check
of
the
discharge
pipe
thermistor.
See
Possible cause:
Faulty discharge pipe thermistor or connector fault.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
1.5.16 H0-00 – Outdoor unit: Voltage/current sensor problem
Trigger
Effect
Reset
Compressor voltage (DC)
is out of range before
start‑up.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
2
Perform a check of the inverter PCB. See
Possible cause:
Faulty inverter PCB.
3
Check if the power supply is conform with the regulations. See
121].
Possible cause:
▪
Faulty or disturbance of the power supply (imbalance >10%),
▪
Power drop,
▪
Short circuit.