Part 6 Service Diagnosis
293
Note(s)
5.2 Low
Pressure
Check
CHECK 2
Referring to the Fault Tree Analysis (FTA) shown below, probe the defective points.
Abnormally dropin
low pressure
(Low evaporating
temperature)
[In cooling]
(
*
1.)
Defective
low pressure
control
Defective
compressor
capacity
control
Defective low pressure
sensor
Defective main PCB
Defective
low pressure
protection
control
Defective low pressure
sensor
Defective hot gas
solenoid valve
Defective main PCB
[In both cooling
and heating]
(
*
2.)
[In cooling]
If the indoor unit
electronic
expansion valve is
throttled too much:
(
*
3.)
Defective indoor
unit electronic
expansion valve
Defective valve coil
Defective valve body
Defective
control
Defective gas pipe
thermistor of indoor unit
Defective liquid pipe
thermistor of indoor unit
Defective main PCB
Defective outdoor
unit electronic
expansion valve
Defective valve coil
Defective valve body
[In heating]
If the outdoor unit
electronic
expansion valve
excessively
throttled:
(
*
4.)
Defective
control
Defective low pressure
sensor
Defective suction pipe
thermistor
Defective main PCB
[In cooling]
Low suction air
temperature of
the evaporator
[In heating]
Low suction air
temperature of
indoor unit
Short circuit
Low room temperature
Defective suction air thermistor of indoor unit
Low suction air temperature of outdoor unit
Defective outdoor air temperature thermistor of outdoor unit
High pipe
resistance
Abnormal piping length
Bent or crushed pipe
Clogging of foreign materials
Stop valve closed
Less
circulation
quantity of
refrigerant
Degradation
in evaporating
capacity
Refrigerant shortage
Moisture choke
Dirty
evaporator
Decreased
airflow rate
Decreased
fan output
Defective fan motor
←Can the fan motor be rotated with hands?
Are the motor coil resistance and insulation normal?
←If a spare PCB is installed, is the
capacity setting properly made?
←Is the air filter clogged?
←Is there any obstacle in the airflow passage?
Defective main PCB
(Including capacity setting)
High
airflow
passage
resistance
Dirty filter
Obstacle
Defective electronic
expansion valve
control
←Is the pressure value checked with the Service Checker
corresponding to the measurement value of the pressure sensor?
←Are the voltage characteristics normal?
←Is the pressure value checked with the Service Checker
corresponding to the measurement value of the pressure sensor?
←Are the coil resistance and insulation normal?
←Are the voltage characteristics normal?
←Are the coil resistance and insulation normal?
←Check for the thermistor resistance and connection.
←Check for the thermistor resistance and connection.
←Are the voltage characteristics normal?
←Are the coil resistance and insulation normal?
←Is the pressure value checked with the Service Checker
corresponding to the measurement value of the pressure sensor?
←Check for the thermistor resistance and connection.
←Is the suction air temperature less than 14°C (57.2°F)?
←Is the room temperature less than 14°C (57.2°F)?
←Is the connector properly connected?
Are the thermistor resistance characteristics normal?
←Is the outdoor air temperature less than –20°C (–4°F)?
←Is the connector properly connected?
Are the thermistor resistance characteristics normal?
←Does the piping length fall in the permissible range?
←Conduct visual checks for pipe conditions.
←Is there any temperature difference caused before and
after the filter or branch pipe?
←Refer to the
CHECK 7
.
←Eliminate moisture by vacuum operation. (Refer to
CHECK 8
)
←Is the heat exchanger clogged?
∗
1: For details of compressor capacity control while in cooling, refer to Compressor PI control
on page 106.
∗
2: The low pressure protection control includes low pressure protection control and hot gas
bypass control.
∗
3: In cooling, the indoor unit electronic expansion valve is used for superheated degree
control.
∗
4: In heating, the outdoor unit electronic expansion valve is used for superheated degree
control of outdoor heat exchanger.
Содержание SkyAir RZR-TA Series
Страница 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Страница 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Страница 321: ...SiUS281811EA 315 Part 7 Appendix 1 Wiring Diagrams 316 1 1 Outdoor Unit 316 1 2 Indoor Unit 320 Part 7 Appendix...
Страница 322: ...Wiring Diagrams SiUS281811EA 316 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RZR18 24TAVJU RZQ18 24TAVJU 3D115455...
Страница 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Страница 324: ...Wiring Diagrams SiUS281811EA 318 Part 7 Appendix RZR30 36 42 48TAVJU RZQ30 36 42 48TAVJU 3D115456...
Страница 325: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 319 RZR30 36 42 48TAVJUA RZQ30 36 42 48TAVJUA 3D124500...
Страница 326: ...Wiring Diagrams SiUS281811EA 320 Part 7 Appendix 1 2 Indoor Unit FCQ18 24 30 36 42 48TAVJU 3D115647A...
Страница 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Страница 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Страница 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...