Troubleshooting by Error Codes
SiUS281811EA
290
Part 6 Service Diagnosis
4.58 System Not Set
Error Code
UF
Applicable
Models
All indoor units
All outdoor units
Method of Error
Detection
On check operation, the number of indoor units in terms of transmission is not corresponding to that
of indoor units that have made changes in temperature.
Error Decision
Conditions
The error is determined as soon as the abnormality aforementioned is detected through checking
the system for any erroneous connection of units on the check operation.
Supposed
Causes
Improper connection of transmission wiring between indoor-outdoor units
Failure to execute check operation
Defective indoor unit PCB
Stop valve is not opened
Troubleshooting
Caution
Is
indoor-outdoor unit
transmission wiring
normal?
Is
indoor-outdoor unit
transmission wiring
normal?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Press
RETURN (BS3)
button
on outdoor unit PCB for 5
seconds or longer.
∗
No operation for max. 12
minutes.
After fixing incorrect wiring,
press and hold the
RETURN
(BS3)
button on the master
outdoor unit PCB for 5
seconds.
∗
The unit will not run for up to
12 minutes.
YES
YES
NO
YES
NO
NO
NO
YES
Is the check
operation carried
out?
Open stop valve.
Replace the indoor unit PCB.
Normal
YES
NO
Are the stop valves
opened?
Are there any other
errors?
Perform test operation again and
press
RETURN (BS3)
button.
Содержание SkyAir RZR-TA Series
Страница 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Страница 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Страница 321: ...SiUS281811EA 315 Part 7 Appendix 1 Wiring Diagrams 316 1 1 Outdoor Unit 316 1 2 Indoor Unit 320 Part 7 Appendix...
Страница 322: ...Wiring Diagrams SiUS281811EA 316 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RZR18 24TAVJU RZQ18 24TAVJU 3D115455...
Страница 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Страница 324: ...Wiring Diagrams SiUS281811EA 318 Part 7 Appendix RZR30 36 42 48TAVJU RZQ30 36 42 48TAVJU 3D115456...
Страница 325: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 319 RZR30 36 42 48TAVJUA RZQ30 36 42 48TAVJUA 3D124500...
Страница 326: ...Wiring Diagrams SiUS281811EA 320 Part 7 Appendix 1 2 Indoor Unit FCQ18 24 30 36 42 48TAVJU 3D115647A...
Страница 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Страница 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Страница 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...