SiUS281811EA
Field Setting from Remote Controller
Part 5 Field Settings and Test Operation
145
1. Field Setting from Remote Controller
Individual function of indoor unit can be changed from the remote controller. At the time of
installation or after service inspection / repair, make the field setting in accordance with the
following description.
Wrong setting may cause error.
(When optional accessory is mounted on the indoor unit, setting for the indoor unit may be required
to change. Refer to information in the option handbook.)
1.1 Wired
Remote
Controller
1.1.1 BRC1E73
1.
Press and hold
Cancel
button for 4
seconds or more.
Service settings menu is displayed.
2.
Select
Field Settings
in the Service
Settings menu, and press
Menu/OK
button.
Field settings screen is displayed.
3.
Highlight the mode, and select desired
“Mode No.” by using
(Up/Down)
button.
4.
In the case of setting per indoor unit
during group control (When Mode No.
such as
20, 21, 22, 23, 25
are selected),
highlight the unit No. and select
“Indoor unit No.” to be set by
using
(Up/Down)
button.
(In the case of group total setting,
this operation is not needed.)
In the case of individual setting per indoor
unit, current settings are displayed. And,
SECOND CODE NO. “ - ” means no
function.
5.
Highlight SECOND CODE NO. of the
FIRST CODE NO. to be changed, and
select desired “SECOND CODE NO.” by
using
(Up/Down)
button. Multiple
identical mode number settings are
available.
In case of setting for all indoor units in the
remote control group, available SECOND
CODE NO. is displayed as “
∗
” which
means it can be changed.
When SECOND CODE NO. is displayed
as “ - ”, there is no function.
<Basic screen>
(1)
<Service Settings menu screen>
(2)
Press
Menu/OK
button.
<Service Settings screen>
(3)
(4)
(5)
(3)
(5)
Press
Menu/OK
button.
FIRST CODE (SW) NO.
SECOND CODE NO.
Press and hold
Cancel
button for 4 seconds or
more during backlight lit.
In the case of individual
setting per indoor unit
In the case of group total
setting
Содержание SkyAir RZR-TA Series
Страница 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Страница 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Страница 321: ...SiUS281811EA 315 Part 7 Appendix 1 Wiring Diagrams 316 1 1 Outdoor Unit 316 1 2 Indoor Unit 320 Part 7 Appendix...
Страница 322: ...Wiring Diagrams SiUS281811EA 316 Part 7 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RZR18 24TAVJU RZQ18 24TAVJU 3D115455...
Страница 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Страница 324: ...Wiring Diagrams SiUS281811EA 318 Part 7 Appendix RZR30 36 42 48TAVJU RZQ30 36 42 48TAVJU 3D115456...
Страница 325: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 319 RZR30 36 42 48TAVJUA RZQ30 36 42 48TAVJUA 3D124500...
Страница 326: ...Wiring Diagrams SiUS281811EA 320 Part 7 Appendix 1 2 Indoor Unit FCQ18 24 30 36 42 48TAVJU 3D115647A...
Страница 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Страница 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Страница 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...