Troubleshooting by Indication on the Remote Controller
SiUS28-902_B
102
Service Diagnosis
3.11 Suction Air Thermistor Abnormality
Remote
Controller
Display
C9
Applicable
Models
FCQ, FHQ, FAQ
Method of Error
Detection
The error is detected by temperature detected by suction air temperature thermistor.
Error Decision
Conditions
When the suction air temperature thermistor becomes disconnected or shorted while the unit is
running
Supposed
Causes
Defective indoor unit thermistor for suction air
Defective indoor unit PCB
Troubleshooting
Note:
Connector and indoor unit PCB
Refer to “Thermistor Resistance / Temperature Characteristics” table on P.161.
Connector is
connected to the
connector(
*
) of the indoor
u
nit PCB.
Resistance
is normal
w
hen
meas
u
red after
disconnecting the thermistor
from the indoor
u
nit
PCB (7.2
~
112
)
Caution
Be s
u
re to t
u
rn off the po
w
er s
w
itch
b
efore connecting or disconnecting
the connector or parts may
b
e damaged.
Replace the indoor
u
nit PCB.
Connect the thermistor and t
u
rn
O
N
again.
N
O
N
O
Replace the thermistor (
*
).
YES
YES
Model
Connector for the suction air thermistor
Symbol
PCB
FCQ
X13A
R1T
A1P
FHQ
X13A
R1T
A1P
FAQ
X19A
R1T
A1P