![Daikin SkyAir FCAHG71GVEB Скачать руководство пользователя страница 18](http://html1.mh-extra.com/html/daikin/skyair-fcahg71gveb/skyair-fcahg71gveb_installer-and-user-manual_3281063018.webp)
7 Configuration
Installer and user reference guide
18
FCAHG71~140GVEB
Split system air conditioners
4P482875-1 – 2017.03
WARNING
Provide adequate measures to prevent that the unit can be
used as a shelter by small animals. Small animals that
make contact with electrical parts can cause malfunctions,
smoke or fire.
5
Reattach the service cover.
▪
Pair type or multi-system.
1 user interface controls 1 indoor unit.
1~ 50 Hz
220-240 V
b
a
e1
c
d
▪
Simultaneous operation system.
1 user interface controls 2
indoor units (indoor units operate simultaneously)
1~ 50 Hz
220-240 V
b
a
e1
c
d
▪
Group control.
1 user interface controls up to 16 indoor units (all
indoor units operate according to the user interface).
1~ 50 Hz
220-240 V
b
a
e1
1~ 50 Hz
220-240 V
b
a
1~ 50 Hz
220-240 V
b
a
c
d
c
d
c
d
▪
2 user interface control.
(2 remote controllers control 1 indoor
unit)
1~ 50 Hz
220-240 V
b
a
e2
e1
c
d
a
Interconnection cable
b
Power supply cable
c
Earth leakage circuit breaker
d
Fuse
e1
Main user interface
e2
Optional user interface
Forced OFF
Transm.
T1 T2
70~90
7
10~15
70~90
10~20
(mm)
10~15
d
e
a
b
e
c
d
c
b
a
Service cover (with wiring diagram on the back)
b
Opening for cables
c
Connection of interconnection cable (including earth)
d
Cable tie
e
Connection of user interface cable
7
Configuration
7.1
Field settings
Make the following field settings so that they correspond with the
actual installation setup and with the needs of the user:
▪ Ceiling height
▪ Air flow direction
▪ Air volume when thermostat control is OFF
▪ Time to clean air filter
Setting: Ceiling height
This setting must correspond with the actual distance to the floor,
capacity class and air flow directions.
▪ For 3-way and 4-way air flows (which require an optional blocking
pad kit), see the installation manual of the optional blocking pad
kit.
▪ For all-round air flow, use the table below.