6 Installation

Installer and user reference guide

17

FCAHG71~140GVEB
Split system air conditioners
4P482875-1 – 2017.03

6.4

Connecting the electrical wiring

6.4.1

About connecting the electrical wiring

Typical workflow

Connecting  the  electrical  wiring  typically  consists  of  the  following
stages:

1

Making  sure  the  power  supply  system  complies  with  the
electrical specifications of the units.

2

Connecting the electrical wiring to the outdoor unit.

3

Connecting the electrical wiring to the indoor unit.

4

Connecting the main power supply.

6.4.2

Precautions when connecting the
electrical wiring

INFORMATION

Also  read  the  precautions  and  requirements  in  the
following chapters:

▪ General safety precautions

▪ Preparation

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

If  the  supply  cord  is  damaged,  it  must  be  replaced  by  the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

6.4.3

Guidelines when connecting the electrical
wiring

Keep the following in mind:

▪ If stranded conductor wires are being used, install a round crimp-

style  terminal  on  the  tip.  Place  the  round  crimp-style  terminal  on
the  wire  up  to  the  covered  part  and  fasten  the  terminal  with  the
appropriate tool.

b

a

a

Stranded conductor wire

b

Round crimp-style terminal

▪ Use the following methods for installing wires:

Wire type

Installation method

Single core wire

c b

c

a

a

A

AA´

a

 Curled single core wire

b

 Screw

c

 Flat washer

Wire type

Installation method

Stranded conductor
wire with round
crimp-style terminal

c b

b

a

c

a

B

B

a

 Terminal

b

 Screw

c

 Flat washer

Tightening torques

Wiring

Screw size

Tightening torque

(N•m)

Interconnection
cable
(indoor↔outdoor)

M4

1.18~1.44

User interface cable

M3.5

0.79~0.97

6.4.4

Specifications of standard wiring
components

Component

Specification

Interconnection cable
(indoor↔outdoor)

Minimum cable section of

2.5 mm² and applicable for

230 V

User interface cable

Vinyl cords with 0.75 to

1.25 mm² sheath or cables

(2‑core wires)

Maximum 500 m

6.4.5

To connect the electrical wiring on the
indoor unit

NOTICE

▪ Follow  the  wiring  diagram  (delivered  with  the  unit,

located at the inside of the service cover).

▪ For instructions on how to connect the decoration panel

and the sensor kit, see the installation manual delivered
with the panel or the kit.

▪ Make  sure  the  electrical  wiring  does  NOT  obstruct

proper reattachment of the service cover.

It is important to keep the power supply and the transmission wiring
separated  from  each  other.  In  order  to  avoid  any  electrical
interference  the  distance  between  both  wiring  should  always  be  at
least 50 mm.

NOTICE

Be sure to keep the power line and transmission line apart
from  each  other.  Transmission  wiring  and  power  supply
wiring may cross, but may not run parallel.

1

Remove the service cover.

2

User  interface  cable

:  Route  the  cable  through  the  frame,

connect the cable to the terminal block, and fix the cable with a
cable tie.

3

Interconnection  cable

  (indoor↔outdoor):  Route  the  cable

through  the  frame,  connect  the  cable  to  the  terminal  block
(make  sure  the  numbers  match  with  the  numbers  on  the
outdoor unit, and connect the earth wire), and fix the cable with
a cable tie.

4

Divide  the  small  sealing  (accessory)  and  wrap  it  around  the
cables to prevent water from entering the unit. Seal all gaps to
prevent small animals from entering the system.

Содержание SkyAir FCAHG71GVEB

Страница 1: ...Installer and user reference guide Split system air conditioners English Installer and user reference guide Split system air conditioners FCAHG71GVEB FCAHG100GVEB FCAHG125GVEB FCAHG140GVEB...

Страница 2: ...ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis...

Страница 3: ...wiring components 17 6 4 5 To connect the electrical wiring on the indoor unit 17 7 Configuration 18 7 1 Field settings 18 8 Commissioning 20 8 1 Overview Commissioning 20 8 2 Precautions when commis...

Страница 4: ...ildren aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning us...

Страница 5: ...s weight and vibration Make sure the area is well ventilated Do NOT block any ventilation openings Make sure the unit is level Do NOT install the unit in the following places In potentially explosive...

Страница 6: ...7 3 6 4 351 3 0 5 74 6 6 27 8 3 0 77 2 6 6 374 3 2 6 54 6 8 29 5 3 2 87 9 6 8 397 3 4 7 38 7 0 31 3 3 4 99 2 7 0 420 3 6 8 27 7 2 33 1 3 6 111 7 2 445 3 8 9 22 7 4 34 9 3 8 124 7 4 470 4 0 10 2 7 6 36...

Страница 7: ...wn Open refrigerant cylinders slowly Charge the refrigerant in liquid form Adding it in gas form may prevent normal operation CAUTION When the refrigerant charging procedure is done or when pausing cl...

Страница 8: ...e all covers are closed before starting up the unit NOTICE Only applicable if the power supply is three phase and the compressor has an ON OFF starting method If there exists the possibility of revers...

Страница 9: ...e Large gas pipe 4 About the units and options 4 1 Overview About the units and options This chapter contains information about Combining outdoor and indoor units Combining the indoor unit with option...

Страница 10: ...ral installation site requirements See the General safety precautions chapter Refrigerant piping requirements length height difference See further in this Preparation chapter INFORMATION The sound pre...

Страница 11: ...orners open optional blocking pad kit required c Air outlet and corners closed optional blocking pad kit required B Minimum and maximum distance to the floor Minimum 2 5 m to avoid accidental touching...

Страница 12: ...ion This chapter describes what you have to do and know on site to install the system Typical workflow Installation typically consists of the following stages Mounting the outdoor unit Mounting the in...

Страница 13: ...een the unit and the ceiling opening C Overlap between the decoration panel and the suspended ceiling Installation guide Use the installation guide to determine the correct vertical position A B C a b...

Страница 14: ...tion 2 Tighten the metal clamp until the screw head is less than 4 mm from the metal clamp part 3 Check for water leaks see To check for water leaks on page 14 4 Install the insulation piece drain pip...

Страница 15: ...to account Avoid anything but the designated refrigerant to get mixed into the refrigerant cycle e g air Only use R32 or R410A1 when adding refrigerant Only use installation tools e g manifold gauge s...

Страница 16: ...and compressors in the refrigerating system and prevents proper operation Set the nitrogen pressure to 20 kPa 0 2 bar just enough so it can be felt on the skin with a pressure reducing valve a b c d e...

Страница 17: ...Terminal b Screw c Flat washer Tightening torques Wiring Screw size Tightening torque N m Interconnection cable indoor outdoor M4 1 18 1 44 User interface cable M3 5 0 79 0 97 6 4 4 Specifications of...

Страница 18: ...ollers control 1 indoor unit 1 50 Hz 220 240 V b a e2 e1 c d a Interconnection cable b Power supply cable c Earth leakage circuit breaker d Fuse e1 Main user interface e2 Optional user interface Force...

Страница 19: ...en4 M C1 C2 2500 h light 10 20 0 01 1250 h heavy 02 No notification 3 02 Individual setting in a simultaneous operation system We recommend using the optional user interface to set the slave unit Perf...

Страница 20: ...kers 8 3 Checklist before commissioning Do NOT operate the system before the following checks are OK You read the complete installation instructions as described in the installer reference guide The i...

Страница 21: ...er supply and outdoor unit between outdoor unit and indoor units between indoor unit and user interface The fuse on the outdoor or indoor unit PCB has blown E3 E4 or L8 The stop valves are closed The...

Страница 22: ...l data Installer and user reference guide 22 FCAHG71 140GVEB Split system air conditioners 4P482875 1 2017 03 11 1 Piping diagram Indoor unit b a c a Liquid pipe connection b Gas pipe connection c Hea...

Страница 23: ...L OVERLOADPROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIPSWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S C LIMITSWITCH F...

Страница 24: ...ech Republic A B C D E FCAHG125 7 83 4 27 13 50 0 25 61 FCAHG140 8 68 4 72 15 50 0 25 61 13 User interface CAUTION Never touch the internal parts of the controller Do not remove the front panel Some p...

Страница 25: ...erant cycle will reverse and energy from inside the building will be used to defrost the outdoor unit coil The indoor unit will indicate defrost operation on the display Hot start In order to prevent...

Страница 26: ...keep the temperature setting at a moderate level Never place objects near the air inlet or the air outlet of the unit It may cause deterioration in the effect or stop the operation Turn off the main...

Страница 27: ...loration and deformation 1 Open the suction grille 1 2 Remove the suction grille 45 1 2 3 Remove the air filter 1 2 3 4 Clean the suction grille Wash with a soft bristle brush and water or neutral det...

Страница 28: ...es service and warranty 17 5 1 Warranty period This product includes a warranty card that was filled in by the dealer at the time of installation The completed card has to be checked by the customer a...

Страница 29: ...to taking apart or cleaning interiors of units by anyone other than our authorised dealers may not be included in the warranty 18 Troubleshooting If one of the following malfunctions occur take the me...

Страница 30: ...eration Moisture generated by defrost becomes steam and is exhausted 18 1 6 Symptom The user interface display reads U4 or U5 and stops but then restarts after a few minutes This is because the user i...

Страница 31: ...can perform or coordinate the required service to the product Installation manual Instruction manual specified for a certain product or application explaining how to install configure and maintain it...

Страница 32: ...4P482875 1 2017 03 Copyright 2017 Daikin...

Отзывы: