Installation manual
5
RZQS71~125B7V3
Split System air conditioners
4PW32097-1
2.
In case of installing multiple units (2 units or more) in lateral
connection per row.
Relation of dimensions of H, A and L are shown in the table below.
R
EFRIGERANT
PIPE
SIZE
AND
ALLOWABLE
PIPE
LENGTH
Selection of piping material
■
Construction material: phosphoric acid deoxidised seamless
copper for refrigerant.
■
Temper grade: use piping with temper grade in function of the
pipe diameter as listed in table below.
■
The pipe thickness of the refrigerant piping should comply with
relevant local and national regulations. The minimal pipe
thickness for R410A piping must be in accordance with the table
below.
O=Annealed
Refrigerant pipe size
Refer to
for double twin system.
■
Main pipe (pipe between outdoor and first branch).
The pipes should have the same size as the outdoor
connections.
■
Pipe between first branch and second branch (L2+L3) (only for
double twin).
■
Pipe between branch and indoor units (L2~L3 for twin, L2~L4 for
triple and L4~L7 for double twin).
These pipe sizes must have the same size as the connected
indoor units pipe sizes. Branch: see marking '
■
' on figures
,
Selection of branch pipe
L
A
L
≤
H
0<L
≤
1/2H
150 (250)
1/2H<L
200 (300)
H<L
Installation impossible
All field piping must be installed by a licensed refrigeration
technician and must comply with relevant local and
national regulations.
To persons in charge of piping work:
■
Be sure to open the shut-off valve after piping
installing and vacuming is complete. (Running the
system with the valve closed may break the
compressor.)
■
It is forbidden to discharge refrigerant into the
atmosphere. Collect the refrigerant in accordance
with the freon collection and destruction law.
■
Do not use flux when brazing the refrigerant piping.
For brazing, use phosphor copper brazing filler metal
(BCuP) which does not require a flux.
(If a chlorine flux is used, the piping will corrode, and if
the flux contains fluoride, it will cause the coolant oil to
deteriorate, adversely affecting the coolant piping
system.
Pipe Ø
Temper grade
of piping material
Minimal thickness t(mm)
9.5
O
0.80
15.9
O
1.00
≥
1000
(1500)
≥
400 (600)
≥
2000
(3000)
A
H
L
Refrigerant pipe size
Gas pipe
Model
Standard size
RZQS71~125
Ø15.9
Liquid pipe
Model
Standard size
RZQS71~125
Ø9.5
Liquid
Ø9.5
Gas
Ø15.9
Twin
KHRQ22M20TA
Triple
KHRQ250H
Double twin
KHRQ22M20TA (3x)