ESIE15-13C
Field Setting from Remote Controller
Field Setting
67
2.3
Settings Contents and Code No. for Indoor Units
You can change the setting of 3 x 3 sensing cassette as mentioned below
The method of field setting, which can be conducted through remote controller, is
established practice, but it is possible only with BRCE52 remote controller.
Mode
No.
First
Code
No.
Description of Setting
Second Code No.
01
02
03
04
05
10
(20)
0
Filter
cleaning
sign
interval
Long life
filter
2,500 hrs.
1,250 hrs.
—
—
—
1
Filter type
Long
Super long
—
—
—
2
Remote controller
thermistor
Enabled
Disabled
—
—
—
3
Filter cleaning sign
Display
No display
—
—
—
7
(note 4)
Detection time for NOT
presence
30 min
60 min
—
—
—
8
(note 5)
Compensation of
suction air temperature
in heating mode
COMPENSATE
(Temperature
[A+2] °C which an
air conditioner
controls when the
temperature of a
remote controller
is A °C)
NO
COMPENSATION
(Temperature [A]
°C which an air
conditioner
controls when the
temperature of a
remote controller
is A °C)
—
—
—
11
(21)
2
Fan OFF at Thermostat
OFF
Normal
OFF
—
—
—
3
Airflow rate setting
during heating
Standard
Slightly up
Up
—
—
4
Automatic operation
mode control
Available
Prohibition
—
—
—
6
(note 6)
Sensitivity of presence
sensor
High
Low
Standard
Sensor does
not work
—
11
(22)
0
Option (KRP1B*) output Compressor
Option
Operation
Malfunction
—
7
(note 6)
Compensation of
temperature around
human body
Floor sensor does
not work
Higher priority on
the air
temperature
Standard
Higher
priority on
the floor
temperature
—
8
(note 6)
Compensation of floor
temperature
-4°C
-2°C
±0°C
+2°C
—
12
(22)
3
Fan speed heating
thermostat OFF
LL-speed
Set-speed
—
—
5
Automatic restart after
power failure reset
Disabled
Enabled
—
—
6
Fan speed cooling
thermostat OFF
LL-speed
Set-speed
—
—
13
(23)
0
High air outlet velocity
(for high ceiling
applications)
Standard
Slightly up
Up
—
1
Selection of airflow
direction
4-way flow
3-way flow
—
—
2
Flap moving in the
swing mode
All 4 flaps
synchronized
—
Two opposite
flaps
synchronized
—
—
4 (*2)
Airflow range setting
Upper
Normal
Lower
—
Содержание RZQG71L9V1
Страница 2: ......
Страница 6: ...ESIE15 13C iv Table of Contents...
Страница 14: ...Introduction ESIE15 13C xii...
Страница 18: ...Outlook Outdoor Units ESIE15 13C 4 General Information 2 Outlook Outdoor Units...
Страница 22: ...Operating range ESIE15 13C 8 General Information...
Страница 108: ...Emergency Operation ESIE15 13C 94 Field Setting...