Daikin RXYSQ5TAY1B Скачать руководство пользователя страница 9

5 Preparation

Installer and user reference guide

9

RXYSQ4~6TAY1B
VRV IV-S system air conditioner
4P482257-1 – 2017.03

4.5.2

Possible combinations of indoor units

In general following type of indoor units can be connected to a VRV
IV-S heat pump system. The list is non-exhaustive and is depending
on both outdoor unit model and indoor unit model combinations.

▪ VRV direct expansion (DX) indoor units (air to air applications).

▪ SA/RA (Sky Air/Residential Air) direct expansion (DX) indoor units

(air to air applications). Further referred to as RA DX indoor units.
These indoor units require a BP box.

▪ AHU  (air  to  air  applications):  EKEXV-kit+EKEQ-box  are  required,

depending on application.

▪ Aircurtain  (air  to  air  applications):  CYV/CAV  (Biddle)  series,

depending on application.

INFORMATION

▪ Combination of VRV DX and RA DX indoor units is not

allowed.

▪ Combination  of  RA  DX  and  AHU  indoor  units  is  not

allowed.

▪ Combination of RA DX and aircurtain indoor units is not

allowed.

4.5.3

Possible options for the outdoor unit

INFORMATION

Refer to the technical engineering data for the latest option
names.

Refrigerant branching kit

Description

Model name

Refnet header

KHRQ22M29H

Refnet joint

KHRQ22M20T

For  the  selection  of  the  optimal  branching  kit,  please  refer  to

"5.3.4 To select refrigerant branch kits" on page 13

.

External control adaptor (DTA104A61/62)

To  instruct  specific  operation  with  an  external  input  coming  from  a
central control the external control adaptor can be used. Instructions
(group  or  individual)  can  be  instructed  for  low  noise  operation  and
power consumption limitation operation.

The external control adapter has to be installed in the indoor unit.

5

Preparation

5.1

Overview: Preparation

This chapter describes what you have to do and know before going
on-site.

It contains information about:

▪ Preparing the installation site

▪ Preparing the refrigerant piping

▪ Preparing the electrical wiring

5.2

Preparing installation site

Do NOT install the unit in places often used as work place. In case
of  construction  works  (e.g.  grinding  works)  where  a  lot  of  dust  is
created, the unit must be covered.

Choose the installation location with sufficient place for carrying the
unit in and out of the site.

5.2.1

Installation site requirements of the
outdoor unit

INFORMATION

Also read the following requirements:

▪ General  installation  site  requirements.  See  the

"General safety precautions" chapter.

▪ Service  space  requirements.  See  the  "Technical  data"

chapter.

▪ Refrigerant 

piping 

requirements 

(length, 

height

difference). See further in this "Preparation" chapter.

CAUTION

Appliance not accessible to the general public, install it in a
secured area, protected from easy access.

This  unit,  both  indoor  and  outdoor,  is  suitable  for
installation 

in 

commercial 

and 

light 

industrial

environment.

NOTICE

This  is  a  class  A  product.  In  a  domestic  environment  this
product  may  cause  radio  interference  in  which  case  the
user may be required to take adequate measures.

NOTICE

The  equipment  described  in  this  manual  may  cause
electronic  noise  generated  from  radio-frequency  energy.
The  equipment  complies  to  specifications  that  are
designed  to  provide  reasonable  protection  against  such
interference.  However,  there  is  no  guarantee  that
interference will not occur in a particular installation.

It  is  therefore  recommended  to  install  the  equipment  and
electric  wires  keeping  proper  distances  away  from  stereo
equipment, personal computers, etc.

b

c

f

d

d

a

c

b

e

(mm)

≥1500

≥1000

≥1000

≥1000 ≥1500

≥1500
≥1500

a

Personal computer or radio

b

Fuse

c

Earth leakage protector

d

User interface

e

Indoor unit

f

Outdoor unit

In  places  with  weak  reception,  keep  distances  of  3  m  or  more  to
avoid  electromagnetic  disturbance  of  other  equipment  and  use
conduit tubes for power and transmission lines.

▪ Select a place where rain can be avoided as much as possible.

▪ Take  care  that  in  the  event  of  a  water  leak,  water  cannot  cause

any damage to the installation space and surroundings.

▪ Choose a location where the hot/cold air discharged from the unit

or the operation noise, will NOT disturb anyone.

▪ Heat  exchanger  fins  are  sharp  and  injury  is  possible.  Choose  an

installation  location  where  there  is  no  risk  for  injury  (especially  in
areas where children play).

Do NOT install the unit in the following places:

Содержание RXYSQ5TAY1B

Страница 1: ...Installer and user reference guide VRV IV S system air conditioner English Installer and user reference guide VRV IV S system air conditioner RXYSQ4TAY1B RXYSQ5TAY1B RXYSQ6TAY1B...

Страница 2: ...6 4 5 Using the stop valve and service port 17 6 4 6 To remove the pinched pipes 18 6 4 7 To connect the refrigerant piping to the outdoor unit 19 6 4 8 To connect the refrigerant branching kit 20 6 5...

Страница 3: ...not work 53 20 2 3 Symptom The fan strength does not correspond to the setting 54 20 2 4 Symptom The fan direction does not correspond to the setting 54 20 2 5 Symptom White mist comes out of a unit...

Страница 4: ...ste batteries are disposed of correctly you will help to prevent potential negative consequences for the environment and human health 1 3 For the installer 1 3 1 General If you are not sure how to ins...

Страница 5: ...ave to operate WARNING Always recover the refrigerant Do NOT release them directly into the environment Use a vacuum pump to evacuate the installation NOTICE After all the piping has been connected ma...

Страница 6: ...tor Failure to do so may cause electric shock or fire When installing the earth leakage protector make sure it is compatible with the inverter resistant to high frequency electric noise to avoid unnec...

Страница 7: ...hat you have to do after the box with the outdoor unit is delivered on site It contains information about Unpacking and handling the units Removing the accessories from the units Keep the following in...

Страница 8: ...utdoor installation and aimed for air to air heat pump applications Specification RXYSQ4 6 Capacity Heating 14 2 18 0 kW Cooling 12 1 15 5 kW Ambient design temperature Heating 20 15 5 C WB Cooling 5...

Страница 9: ...g works where a lot of dust is created the unit must be covered Choose the installation location with sufficient place for carrying the unit in and out of the site 5 2 1 Installation site requirements...

Страница 10: ...the outdoor unit is exposed to direct sea winds install a windbreaker Height of windbreaker 1 5 height of outdoor unit Mind the service space requirements when installing the windbreaker a b c d c d...

Страница 11: ...d leak The unit of measurement of the concentration is kg m3 the weight in kg of the refrigerant gas in 1 m3 volume of the occupied space Compliance to the local applicable regulations and standards f...

Страница 12: ...6 4 mm 1 4 9 5 mm 3 8 12 7 mm 1 2 Annealed O 0 80 mm t 15 9 mm 5 8 Annealed O 0 99 mm 19 1 mm 3 4 22 2 mm 7 8 Half hard 1 2H 0 80 mm a Depending on the applicable legislation and the unit s maximum w...

Страница 13: ...ge 12 Refnet joint at first branch counting from outdoor unit When using refnet joints at the first branch counted from the outdoor unit side choose from the following table in accordance with the cap...

Страница 14: ...imum height difference indoor indoor Examples H2 Limit 15 m 15 m Maximum height difference outdoor BP Example 2 H3 Limit N A 30 m Maximum height difference BP BP Example 2 H4 Limit N A 15 m Maximum he...

Страница 15: ...r and all indoors 600 m If the total transmission wiring exceeds these limits it may result in communication error 6 Installation 6 1 Overview Installation This chapter describes what you have to do a...

Страница 16: ...in order to avoid ice accumulation Prepare a water drainage channel around the foundation to drain waste water surrounding the unit Avoid drain water flowing over the footpath so that it does not beco...

Страница 17: ...egardless of the period INFORMATION Do NOT open the refrigerant stop valve before checking the refrigerant piping When you need to charge additional refrigerant it is recommended to open the refrigera...

Страница 18: ...ing the service port make sure to tighten the service port cover securely For the tightening torque refer to the table below Check for refrigerant leaks after tightening the service port cover Tighten...

Страница 19: ...a with screw b a b 2 Choose a piping route a b c or d a b c d 3 If you have chosen the downwards piping route Drill a 4 and remove the knockout hole b Cut out the slits c with a metal saw c c b a 4 6...

Страница 20: ...ll initialise This means that they will close Leak test and vacuum drying of field piping and indoor units is impossible when this happens Therefore there will be explained 2 methods for initial insta...

Страница 21: ...est for leaks by applying a bubble test solution to all piping connections 3 Discharge all nitrogen gas NOTICE Make sure to use a recommended bubble test solution from your wholesaler Do not use soap...

Страница 22: ...perly NOTICE Be sure to turn on the power 6 hours before operation in order to have power running to the crankcase heater and to protect the compressor NOTICE If operation is performed within 12 minut...

Страница 23: ...refrigerant in manual additional refrigerant charge mode instructions Charging refrigerant in manual additional refrigerant charge mode The remaining additional refrigerant charge can be charged by op...

Страница 24: ...onsists of the following stages 1 Making sure the power supply system complies with the electrical specifications of the units 2 Connecting the electrical wiring to the outdoor unit 3 Connecting the e...

Страница 25: ...tor Install power cables at least 1 metre away from televisions or radios to prevent interference Depending on the radio waves a distance of 1 metre may not be sufficient WARNING After finishing the e...

Страница 26: ...ical wiring on the outdoor unit NOTICE Follow the wiring diagram delivered with the unit located at the inside of the service cover Make sure the electrical wiring does NOT obstruct proper reattachmen...

Страница 27: ...e as shown in figure below a b c d e a Liquid pipe b Gas pipe c Insulator d Transmission wiring F1 F2 e Finishing tape 6 9 2 To close the outdoor unit NOTICE When closing the outdoor unit cover make s...

Страница 28: ...SET For field setting BS3 RETURN For field setting BS4 TEST For test operation BS5 RESET For resetting the address when the wiring is changed or when an additional indoor unit is installed Display Th...

Страница 29: ...lay Mode 2 You can change the value of setting 2 8 Te target temperature during cooling operation to 4 8 C as follows Action Button display 1 Start from the default situation 2 Select mode 2 BS1 5 s 3...

Страница 30: ...ecked again through this monitoring settings For the content or reason behind the malfunction code see 11 3 Solving problems based on error codes on page 38 where most relevant malfunction codes are e...

Страница 31: ...ow noise setting and level during night time By changing this setting you activate the automatic low noise operation function of the unit and define the level of operation Depending on the chosen leve...

Страница 32: ...y consumption and comfort No matter which control is selected variations on the behaviour of the system are still possible due to protection controls to keep the unit operating under reliable conditio...

Страница 33: ...se of cooling operation the evaporating temperature is allowed to go down to 6 C on temporary base depending on the situation In case of heating operation the condense temperature is allowed to go up...

Страница 34: ...orating temperature Quick Powerful Mild Room temperature evolution A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful 7 3 4 Example Automatic mode d...

Страница 35: ...ting up the unit Field wiring Be sure that the field wiring has been carried out according to the instructions described in the chapter 6 8 Connecting the electrical wiring on page 24 according to the...

Страница 36: ...essure equalisation Cooling start up control Cooling stable condition Communication check Stop valve check Pipe length check Pump down operation Unit stop INFORMATION During the test operation it is n...

Страница 37: ...al operation will not be performed For details refer to the wiring diagram labelled on the back of the service cover Pay attention to the fan It is dangerous to inspect the unit while the fan is runni...

Страница 38: ...vercharge Open the stop valve on both the gas and liquid side Recalculate the required amount of refrigerant from the piping length and correct the refrigerant charge level by recovering any excessive...

Страница 39: ...or unit is connected correctly Faulty wiring to Q1 Q2 Check Q1 Q2 wiring System mismatch Wrong type of indoor units combined R410A R407C RA etc Indoor unit malfunction Check if other indoor units have...

Страница 40: ...diagram Wiring diagram 13 2 Dimensions Outdoor unit dimensions in mm 191 142 67 95 940 223 30 16 55 350 160 95 61 55 145 160 30 68 89 84 68 19 48 44 53 90 13 67 80 54 395 47 52 1430 54 95 60 320 89 6...

Страница 41: ...B HU HB HD HD HU 100 1000 1000 500 HU HD HU 200 1000 1000 500 HD HU 200 1700 1000 500 HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 5...

Страница 42: ...A1 If there is danger of drainage dripping and freezing between the upper and lower units A2 Then install a roof between the upper and lower units Install the upper unit high enough above the lower u...

Страница 43: ...erant charge f Stop valve gas g Stop valve liquid h Cable tie mountings to fix the field wiring with cable ties to ensure stress relief i Subcool heat exchanger j Accumulator k Fan A1P Printed circuit...

Страница 44: ...g Heat exchanger h Service port high pressure i Oil separator j Capillary tube 2 k Service port refrigerant charge M1C Compressor M1F M2F Fan motor R1T Thermistor air R2T Thermistor suction 1 R3T The...

Страница 45: ...HT RED TO MULTI UNIT TO OUT D TO IN D INDOOR OUTDOOR Note 5 TERMINAL OF M1C LAYOUTOF M1F M2F M1C L1R EL COMPO BOX DETAILOF EL COMPO BOX ARROW VIEW OUTER SHELL FRONT MARK BLU MARK RED MARK RED EL COMPO...

Страница 46: ...stor air R2T Thermistor suction 1 R3T Thermistor discharge R4T Thermistor heat exchanger de icer R5T Thermistor subcool heat exchanger R6T Thermistor liquid pipe R7T Thermistor suction 2 S1NPH High pr...

Страница 47: ...ired to connect Residential Air RA or Sky Air SA direct expansion DX indoor units f Residential Air RA direct expansion DX indoor units g User interface wireless dedicated depending on indoor unit typ...

Страница 48: ...ation the refrigerant cycle will reverse and energy from inside the building will be used to defrost the outdoor unit coil The indoor unit will indicate defrost operation on the displays Hot start In...

Страница 49: ...user interfaces as the master user interface The displays of slave user interfaces show change over under centralised control and slave user interfaces automatically follow the operation mode directed...

Страница 50: ...ation methods Basic The refrigerant temperature is fixed independent from the situation It corresponds to the standard operation which is known and can be expected from under previous VRV systems Auto...

Страница 51: ...unit Do not use the system until a service person confirms that the portion where the refrigerant leaks is repaired 19 4 After sales service and warranty 19 4 1 Warranty period This product includes...

Страница 52: ...oting If one of the following malfunctions occur take the measures shown below and contact your dealer WARNING Stop operation and shut off the power if anything unusual occurs burning smells etc Leavi...

Страница 53: ...on outdoor De icing temperature sensor malfunction outdoor Liquid temperature sensor after subcool HE malfunction outdoor Liquid temperature sensor coil malfunction outdoor Gas temperature sensor afte...

Страница 54: ...stop When the drain pump optional accessories is in operation this noise is heard A pishi pishi squeaking sound is heard when the system stops after heating operation Expansion and contraction of pla...

Страница 55: ...relevant and applicable for a certain product or domain Service company Qualified company which can perform or coordinate the required service to the product Installation manual Instruction manual sp...

Страница 56: ...4P482257 1 2017 03 Copyright 2017 Daikin...

Отзывы: