7 Configuration
Installer and user reference guide
30
RXYSQ4~6TAY1B
VRV IV-S system air conditioner
4P482257-1 – 2017.03
Value / Description
H7P
Shows the status of power consumption limitation operation.
OFF
Unit is currently not operating under power
consumption limitations.
ON
Unit is currently operating under power consumption
limitation.
Power consumption limitation reduces the power
consumption of the unit compared to nominal operating
conditions.
Power consumption limitation can be set in mode 2. There
are two methods to activate power consumption limitation of
the outdoor unit system.
▪ The first method is to enable a forced power consumption
limitation by field setting. The unit will always operate at
the selected power consumption limitation.
▪ The second method is to enable power consumption
limitation based on an external input. For this operation
an optional accessory is required.
7‑LEDs display – Mode 1 (H1P flashing)
You can read out the following information:
Setting
(
)
Value / Description
[1‑5]
Shows the total number of
connected indoor units.
It can be convenient to check if
the total number of indoor units
which are installed match the
total number of indoor units
which are recognised by the
system. In case there is a
mismatch, it is advised to check
the communication wiring path
between outdoor and indoor units
(F1/F2 communication line).
[1‑14]
Shows the latest malfunction
code.
When the latest malfunction
codes were reset by accident on
an indoor unit user interface, they
can be checked again through
this monitoring settings.
For the content or reason behind
the malfunction code see
"11.3 Solving problems based on
error codes" on page 38
, where
most relevant malfunction codes
are explained. Detailed
information about malfunction
codes can be consulted in the
service manual of this unit.
To obtain more detailed
information about the malfunction
code, press BS2 up to 3 times.
[1‑15]
Shows the 2nd last malfunction
code.
[1‑16]
Shows the 3rd last malfunction
code.
7.2.8
Mode 2: Field settings
In mode 2 you can make field settings to configure the system.
For more information and advice about the impact of settings [2‑8], [2‑9], [2‑41] and [2‑42], see
"7.3 Energy saving and optimum operation" on
.
Setting
(=
binary)
Value
Description
[2‑8]
T
e
target temperature during
cooling operation.
(= binary 3)
(default)
Auto
6°C
8°C
9°C
10°C
11°C
[2‑9]
T
c
target temperature during
heating operation.
(= binary 1)
(default)
Auto
(= binary 4)
43°C
(= binary 2)
46°C
Setting
(=
binary)
Value
Description
[2‑12]
Enable the low noise function
and/or power consumption
limitation via external control
adaptor (DTA104A61/62).
If the system needs to be
running under low noise
operation or under power
consumption limitation
conditions when an external
signal is sent to the unit, this
setting should be changed.
This setting will only be
effective when the optional
external control adaptor
(DTA104A61/62) is installed
in the indoor unit.
(= binary 1)
(default)
Deactivated.
(= binary 2)
Activated.
[2‑18]
Fan high static pressure
setting.
In order to increase the static
pressure the outdoor unit fan
is delivering, this setting
should be activated. For
details about this setting, see
technical specifications.
(= binary 1)
(default)
Deactivated.
(= binary 2)
Activated.