6 Installation
Installer and user reference guide
15
RXYSQ4~Y1B
VRV IV-S system air conditioner
4P404676-1A – 2016.03
Example 1 (VRV DX indoor units)
Example 2 (RA DX indoor units)
Example 1.1
a
A
h
i
j
k
l
m
n
B
C
D
E
F
G
p
b
c
d
e
f
1
2
3
4
5
6
7
8
g
H1
H2
H3
a
c
d
f
H1
BP1
g
h
b
A
l
m
BP3
18
17
13
12
11
H4
e
i
BP2
j
k
16
15
14
H2
H5
Example 1.2
a
b
c
d
e
f
i
k
j
g
h
A
B
1
2
3
4
5
6
7 8
H1
H2
Example 1.3
a
c
b
d
e
f
i
g
h
1
2
3
4
5
6
7
8
H1
H2
Refnet joint
Refnet header
BP box
1~8
VRV DX indoor units
11~18
RA DX indoor units
5.4
Preparing electrical wiring
5.4.1
About electrical compliance
Only for RXYSQ4~6_V1
Equipment complying with EN/IEC 61000‑3‑12 (European/
International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage
systems with input current >16 A and ≤75 A per phase.).
5.4.2
Safety device requirements
The power supply must be protected with the required safety
devices, i.e. a main switch, a slow blow fuse on each phase and an
earth leakage protector in accordance with the applicable legislation.
Selection and sizing of the wiring should be done in accordance with
the applicable legislation based on the information mentioned in the
table below.
Model
Minimum circuit
ampacity
Recommended
fuses
Power supply
RXYSQ4_V1
29.1 A
32 A
1~ 50 Hz
220-240 V
RXYSQ5_V1
RXYSQ6_V1
RXYSQ4_Y1
14.1 A
16 A
3N~ 50 Hz
380-415 V
RXYSQ5_Y1
RXYSQ6_Y1
Transmission wiring
Transmission wiring
Vinyl cords with 0.75 to 1.25 mm²
sheath or cables (2‑core wires)
Maximum wiring length
(= distance between outdoor and
furthest indoor unit)
300 m
Total wiring length
(= distance between outdoor and
all indoors)
600 m
If the total transmission wiring exceeds these limits, it may
result in communication error.
6
Installation
6.1
Overview: Installation
This chapter describes what you have to do and know on-site to
install the system.
Typical workflow
Installation typically consists of the following stages:
▪ Mounting the outdoor unit.
▪ Mounting the indoor units.
▪ Connecting the refrigerant piping.
▪ Checking the refrigerant piping.
▪ Charging refrigerant.
▪ Connecting the electrical wiring.
▪ Finishing the outdoor installation.
▪ Finishing the indoor installation.
INFORMATION
For installation of the indoor unit (mounting the indoor unit,
connecting the refrigerant piping to the indoor unit,
connecting the electrical wiring to the indoor unit …), see
the installation manual of the indoor unit.
6.2
Opening the units
6.2.1
About opening the units
At certain times, you have to open the unit.
Example:
▪ When connecting the refrigerant piping
▪ When connecting the electrical wiring
▪ When maintaining or servicing the unit