4P404224-1C – 2019.07
NOTICE
If the power of some units is turned off, the charging
procedure cannot be finished properly.
NOTICE
Be sure to turn on the power 6 hours before operation in
order to have power running to the crankcase heater and
to protect the compressor.
NOTICE
If operation is performed within 12 minutes after the indoor
and outdoor units are turned on, the compressor will not
operate before the communication is established in a
correct way between outdoor unit(s) and indoor units.
NOTICE
Before starting charging procedures, check if the 7‑LEDs
display is as normal (see
"7.2.4 To access mode 1 or 2" on
), and there is no malfunction code on the user
interface of the indoor unit. If a malfunction code is
present, see
"11.3 Solving problems based on error
.
NOTICE
Make sure all connected indoor units are recognised
(setting [1‑5]).
NOTICE
Close the front panel before any refrigerant charge
operation is executed. Without the front panel attached the
unit cannot judge correctly whether it is operating properly
or not.
NOTICE
In case of maintenance and the system (outdoor unit+field
indoor units) does not contain any refrigerant any
more (e.g., after refrigerant reclaim operation), the unit has
to be charged with its original amount of refrigerant (refer
to the nameplate on the unit) and the determined additional
refrigerant amount.
6.7.3
To determine the additional refrigerant
amount
INFORMATION
For final charge adjustment in a test laboratory, contact
your dealer.
Formula:
R=[(X
1
×
Ø9.5
)×0.059+(X
2
×
Ø6.4
)×0.022]
R
Additional refrigerant to be charged [in kg and rounded off
to 1 decimal place]
X
1...2
Total length [m] of liquid piping size at
Øa
Metric piping.
When using metric piping, replace the weight factors
in the formula by the ones from the following table:
Inch piping
Metric piping
Piping
Weight factor
Piping
Weight factor
Ø6.4 mm
0.022
Ø6 mm
0.018
Ø9.5 mm
0.059
Ø10 mm
0.065
Connection ratio requirements.
When selecting indoor units, the
connection ratio must comply with the following requirements. For
more information, see the technical engineering data.
Indoor units
Total CR
(a)
CR per type
(b)
VRV DX
RA DX
VRV DX
50~130%
50~130%
—
Indoor units
Total CR
(a)
CR per type
(b)
VRV DX
RA DX
RA DX
80~130%
—
80~130%
(a)
Total CR = Total indoor unit capacity connection ratio
(b)
CR per type = Allowable capacity connection ratio per
indoor unit type
6.7.4
To charge refrigerant
To speed up the refrigerant charging process, it is in case of larger
systems recommended to first pre-charge a portion of refrigerant
through the liquid line before proceeding with the manual charging. It
can be skipped, but charging will take longer then.
Pre-charging refrigerant
Pre-charging can be done without compressor operation, by
connecting the refrigerant bottle to the service port of the liquid stop
valve.
1
Connect as shown. Make sure that all outdoor unit stop valves,
as well as valve A are closed.
p< p>
N2
C
b
c
e
a
g
f
d
A
B
a
Pressure reducing valve
b
Nitrogen
c
Weighing scales
d
Refrigerant R410A tank (siphon system)
e
Vacuum pump
f
Liquid line stop valve
g
Gas line stop valve
A
Valve A
B
Valve B
C
Valve C
2
Open valves C and B.
3
Pre‑charge refrigerant until the determined additional refrigerant
amount is reached or pre‑charging is not possible anymore, and
then close valves C and B.
4
Do one of the following:
If
Then
The determined additional
refrigerant amount is
reached
Disconnect the manifold from
the liquid line.
You do not have to perform the
"Charging refrigerant (in
manual additional refrigerant
charge mode)" instructions.
Too much
refrigerant is
charged
Recover refrigerant.
Disconnect the manifold from
the liquid line.
You do not have to perform the
"Charging refrigerant (in
manual additional refrigerant
charge mode)" instructions.
The determined additional
refrigerant amount is
not
reached
yet
Disconnect the manifold from
the liquid line.
Continue with the "Charging
refrigerant (in manual
additional refrigerant charge
mode)" instructions.