Troubleshooting by Error Code
Service Diagnosis
278
3.63 Improper Combination of Indoor Unit and Outdoor Unit,
Indoor Unit and Remote Controller
Error Code
UA
Applicable
Models
All indoor unit models
All outdoor unit models
Method of Error
Detection
A difference occurs in data by the type of refrigerant between indoor and outdoor units.
The number of indoor units connected is out of the allowable range.
Error Decision
Conditions
The error decision is made as soon as either of the abnormalities aforementioned is detected.
Supposed
Causes
Excess of connected indoor units
Defective outdoor unit PCB
Mismatch of the refrigerant type of indoor and outdoor unit.
Setting of outdoor unit PCB was not carried out after replacing to spare PCB.
Содержание RXYQ-TA Series
Страница 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Страница 320: ...Wiring Diagrams SiUS341615E 307 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72TAYDU 3D106438A...
Страница 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Страница 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Страница 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Страница 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Страница 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Страница 334: ...Wiring Diagrams SiUS341615E 321 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C...
Страница 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Страница 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...