SiUS341615E
Troubleshooting by Error Code
Service Diagnosis
214
3.28 Missing of Leakage Detection Core
Error Code
E2
Applicable
Models
All outdoor unit models
Method of Error
Detection
Detect error according to whether or not there is continuity across the connector (X101A).
Error Decision
Conditions
When no current flows at the time of turning ON the power supply.
Supposed
Causes
Disconnection of connector (X101A)
Wiring disconnection
Defective outdoor unit main PCB
Troubleshooting
Sub code: -06 to -08
NO
YES
Is the system reset to
normal?
Is X101A connected?
The error is considered to have
resulted from external factors
other than failures (e.g. noise).
Turn OFF the power supply, and
then disconnect compressor leads.
YES
Properly connect the connector.
NO
Replace the outdoor unit main
PCB (A1P).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Ensure the unit
corresponding to the error
code
E2
in monitor mode.
E02-06: Master
E02-07: Slave 1
E02-08: Slave 2
Содержание RXYQ-TA Series
Страница 1: ...Service Manual SiUS341615E RXYQ72 408TAYDU RXYQ72 408TATJU Heat Pump 60 Hz...
Страница 320: ...Wiring Diagrams SiUS341615E 307 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72TAYDU 3D106438A...
Страница 321: ...SiUS341615E Wiring Diagrams Appendix 308 RXYQ96 120TAYDU 2D106439A...
Страница 322: ...Wiring Diagrams SiUS341615E 309 Appendix RXYQ144 168TAYDU 2D106440A...
Страница 323: ...SiUS341615E Wiring Diagrams Appendix 310 RXYQ72TATJU 3D106435A...
Страница 324: ...Wiring Diagrams SiUS341615E 311 Appendix RXYQ96 120TATJU 2D106436A...
Страница 325: ...SiUS341615E Wiring Diagrams Appendix 312 RXYQ144 168TATJU 2D106437A...
Страница 334: ...Wiring Diagrams SiUS341615E 321 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C...
Страница 335: ...SiUS341615E Wiring Diagrams Appendix 322 VAM1200GVJU 3D073270C...
Страница 336: ...Revision History Month Year Version Revised contents 02 2017 SiUS341615E First edition...